Omron CS1W-ETN21 operation manual 207

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 232
Image 232

Error Log

 

 

 

Section 8-3

 

 

 

 

 

 

Error

Meaning

Detailed error code

Correction

EE-

code

 

 

 

 

 

PROM

 

1st byte

 

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

 

03C4

Server connection error

00: DNS

 

01: Specified

Take either of the following mea-

---

 

 

01: SMTP

 

host does not

sures.

 

 

 

 

exist

• Correct the settings for each

 

 

 

02: POP3

 

 

 

 

 

02: No ser-

 

 

 

 

server.

 

 

 

03: SNTP

 

 

 

 

 

vice at speci-

• Inspect the communications path

 

 

 

 

 

 

 

 

 

 

fied host

(Ethernet Unit, cable connec-

 

 

 

 

 

03: Timeout

tions, hub, router, server), and

 

 

 

 

 

04: Closed

correct the situation that is caus-

 

 

 

 

 

ing the error.

 

 

 

 

 

unilaterally by

 

 

 

 

 

 

 

 

 

 

 

host

 

 

 

 

 

 

05: Cannot

 

 

 

 

 

 

connect

 

 

 

 

 

 

because

 

 

 

 

 

 

account infor-

 

 

 

 

 

 

mation does

 

 

 

 

 

 

not match

 

 

 

 

 

 

06: Host

 

 

 

 

 

 

name resolu-

 

 

 

 

 

 

tion error

 

 

 

 

 

 

07: Transmis-

 

 

 

 

 

 

sion error

 

 

 

 

 

 

08: Recep-

 

 

 

 

 

 

tion error

 

 

 

 

 

 

09: Other

 

 

 

 

 

 

error

 

 

 

 

 

 

 

 

03C5

Mail communications error

F101: Mail too large

Refer to the Operation Manual,

---

 

 

F102: Mail received from

Construction of Applications: Cre-

 

 

 

ating FINS Applications, and cor-

 

 

 

non-specified address

 

 

 

rect the remote node (i.e., the

 

 

 

F103: Mail subject error

 

 

 

application on the personal com-

 

 

 

F104: Non-specified com-

 

 

 

puter).

 

 

 

mand received

 

 

 

 

 

F106: Mail format (header)

 

 

 

 

error

 

 

 

 

 

F107: Mail format (body)

 

 

 

 

error

 

 

 

 

 

F201: Parameter error

 

 

 

 

F301: Decoding error

 

 

 

 

F302: File attachment error

 

 

 

 

(filename error, data format

 

 

 

 

error, I/O memory write size

 

 

 

 

error)

 

 

 

 

 

F303: No attached file

 

 

 

 

F304: Non-specified file

 

 

 

 

attachment received

 

 

 

 

F305: File attachment too

 

 

 

 

large

 

 

 

 

 

Other: FINS error response

 

 

 

 

code

 

 

 

 

 

 

 

 

03C6

Clock data write error

0001: Clock data could not

Clear the CPU Unit error.

---

 

 

be refreshed because of a

 

 

 

 

CPU Unit error.

 

 

 

 

 

 

 

 

 

 

0002: Clock data could not

Refer to the Operation Manual,

---

 

 

be refreshed because the

Construction of Applications:

 

 

 

CPU Unit could not write

Automatic Clock Adjustment

 

 

 

clock data in that operation

Function, and check the operat-

 

 

 

mode.

 

ing conditions.

 

 

 

 

 

 

 

 

207

Page 232
Image 232
Omron CS1W-ETN21 operation manual 207