Omron CS1W-ETN21 operation manual Ftp, Confidential

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 88
Image 88

Setup

 

 

 

Section 3-1

 

 

 

 

 

 

Item

Contents

Default

 

 

 

 

Destination IP Address

Select to dynamically change the remote (destination) IP address for

Checked

(Change Dynamically)

FINS/UDP. To prohibit dynamic changes, deselect this box.

(Change Dynami-

 

cally)

 

 

 

 

 

 

 

 

 

Baud Rate

 

 

Select the Ethernet baud rate for the Ethernet Unit.

Auto

 

 

 

Select either automatic detection or 10Base-T. (For 100Base-TX, select

 

 

 

 

automatic detection.)

 

 

 

 

 

TCP/IP keep-alive

Set the liveness-checking interval. When socket services using either

0

 

 

 

FINS/TCP or TCP/IP are used, the connection will be terminated if there

(120 minutes)

 

 

 

is no response from the remote node (either a server or client) within the

 

 

 

 

time set here. (Enabled for socket services using FINS/TCP or TCP/IP

 

 

 

 

only.)

 

 

 

 

Setting range: 0 to 65,535 minutes

 

 

 

 

This setting applies to the keep-alive setting for each connection set

 

 

 

 

with the FINS/TCP tab.

 

 

 

 

 

IP Address Table

Set the IP address table that defines the relationship between FINS

None

 

 

 

node addresses and IP addresses.

 

 

 

 

With FINS/UDP, this is enabled only when the IP address table method

 

 

 

 

is set as the IP address conversion method.

 

 

 

 

 

IP Router Table

Set when the Ethernet Unit is to communicate through the IP router with

None

 

 

 

nodes on another IP network segment.

 

 

 

 

 

 

FTP

 

Login

Sets the login name for connecting to the Ethernet Unit by FTP.

None

 

 

 

 

 

 

 

Password

Sets the password for connecting to the Ethernet Unit by FTP.

None

 

 

 

 

(“CONFIDENTIAL”)

 

 

 

 

 

 

 

Port No.

Set the FTP port number for the Ethernet Unit.

0

 

 

 

There is normally no need to change this number.

(Number 21 is

 

 

 

Two ports are used for FTP: a control port and a data transfer port. This

used.)

 

 

 

setting sets only the control port, and then the data transfer port uses

 

 

 

 

the number that is one less than the control port.

 

 

 

 

 

 

Note (1) The setting to enable or disable dynamic changing of remote IP address-

es is available for Ethernet Units with Unit Ver. 1.3 or later.

(2)Make settings using the unit settings function in the CX-Programmer (to be included in version 5.0 and higher) or using the Web function (refer to Appendix G Ethernet Unit Web Function).