Omron CS1W-ETN21 operation manual Results Storage Format Parameters

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 204
Image 204

Command/Response Reference

Section 7-3

Response Block

27 13

Command Response

code code

Results Storage Format

Parameters

Socket Option (Command)

TCP Socket Number (Command)

Results Storage Area (Command)

Number of Bytes Sent

(Command, Results

Storage Area)

Data Sent (Command)

Response

Number of

code

bytes sent

The socket option specified as 1 byte. The setting is not valid for this com- mand. Set to 0.

The TCP socket number to send the data specified as 1 byte between 1 and 8.

The area in which the results of the command execution are stored. The first byte specifies the memory area and data type (variable type). The 2nd to 4th bytes specify the beginning address of the results storage area. Refer to page 158 for details about the variable types and addresses that can be spec- ified.

The number of bytes in the data sent specified between 0 and 1,984. The results storage area stores the actual number of bytes sent.

Specifies the data to be sent.

Response Codes

Response code

Description

 

 

0000

Normal

 

 

0105

Local IP address setting error

 

 

0302

CPU Unit error; execution not possible.

 

 

1001

Command too large

 

 

1002

Command too small

 

 

1003

The number of bytes sent does not match the amount of data.

 

 

1100

The TCP socket number or number of bytes sent is out of

 

range.

 

 

1101

The variable type for the results storage area is out of range.

 

 

1103

Non-zero bit address specified for the results storage area.

 

 

220F

The specified socket is sending data.

 

 

2210

No connection could be established to the specified socket.

 

 

2211

High traffic at Unit; cannot execute service.

 

 

179