IP Addresses in FINS Communications

Section 5-2

5-2-2 Pairing Addresses in Internal Tables

FINS/UDP Communications Methods

Automatic Generation (Dynamic)

When the Ethernet Unit is turned ON or restarted, the following values are set for addresses in the internal table.

• Remote IP address:

Local IP address network number + remote

 

FINS node address

• Remote UDP port number: UDP port number set for local Unit

• Connection method:

FINS/UDP

With the dynamic method, data in an internal table that has been generated can be dynamically converted according to FINS messages received from remote nodes. This is enabled when the remote node is a device such as a personal computer and IP addresses are dynamically changed by a method such as DHCP.

Ethernet Unit

CPU Unit

Personal computer

 

 

Must be fixed.

Change

 

registration

 

Local FINS node number

Automatic generation

(dynamic setting)

Can be changed.

Internal table

 

Local IP address

Remote IP address

Local IP address

 

IP address FINS command

Ethernet

 

IP address FINS response

Remote FINS node number

Local FINS node number

For the remote IP address, a response is returned to the changed IP address.

Automatic Generation (Static)

With the static method as well, the following values are set for addresses in the internal table when the Ethernet Unit is turned ON or restarted.

• Remote IP address:

Local IP address network number + remote

 

FINS node address

• Remote UDP port number: UDP port number set for local Unit

• Connection method:

FINS/UDP

With the static method, however, data in an internal table that has been gener- ated is not freely changed.

 

 

Ethernet Unit

CPU Unit

Personal computer

 

 

Remote FINS node number

 

 

 

 

Must be fixed.

 

Local FINS node number

 

 

 

Local FINS node number

 

Automatic generation

 

(static setting)

 

Must be fixed.

 

Internal table

 

 

Local IP address

 

Remote IP address

Local IP address

 

 

IP address FINS command

Ethernet

 

IP address FINS response