Omron CS1W-ETN21 operation manual 224

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 249
Image 249

Troubleshooting with Response Codes

 

Section 8-5

 

 

 

 

 

 

Main code

Sub-code

Check point

Probable cause

Remedy

 

 

 

 

 

 

03: Communi-

01: Communica-

ERC indicator on

Error occurred in the communi-

Take corrective action, referring

cations con-

tions controller

the Controller

cations controller, ERC indica-

to troubleshooting procedures in

troller error

error

 

tor is lit.

this section.

 

 

 

 

 

 

 

02: CPU Unit

Remote CPU Unit

CPU Unit error occurred in the

Check CPU Unit indicators at the

 

error

indicators

PLC at the remote node.

remote node and clear the error

 

 

 

 

 

in the CPU Unit (refer to the PC’s

 

 

 

 

 

operation manuals)

 

 

 

 

 

 

 

04: Unit number

Unit number

Unit number setting error

Make sure the unit number is

 

setting error

 

 

within the specified range and

 

 

 

 

 

that the same unit number is not

 

 

 

 

 

used twice in the same network.

 

 

 

 

 

 

04: Not exe-

01: Unsupported

Command code

An undefined command has

Check the command code and

cutable

command

 

been used.

be sure the command is sup-

(Service not

 

 

 

 

ported by the Unit to which you

 

 

 

 

are sending it.

supported.)

 

 

 

 

 

 

 

 

 

 

 

 

FINS header

A short frame (4 bytes) is being

Check the FINS header frame

 

 

 

frame length

used for the FINS header

length. The Ethernet Unit does

 

 

 

 

frame.

not support short headers.

 

 

 

 

 

05: Routing

01: Routing table

Routing tables

Remote node is not set in the

Set the destination address in

error

setting error

 

routing tables.

the routing tables.

 

 

 

 

 

 

02: Routing

Routing tables

Routing tables aren’t registered

Set routing tables at the local

 

tables not regis-

 

completely.

node, remote node, and any

 

tered

 

 

relay nodes.

 

 

 

 

 

 

03: Routing table

Routing tables

Routing table error

Set the routing tables correctly.

 

error

 

 

 

 

 

 

 

 

 

04: Too many

Network configu-

The maximum number of relay

Redesign the network or recon-

 

relays

ration

nodes (2) was exceeded in the

sider the routing table to reduce

 

 

 

 

command.

the number of relay nodes in the

 

 

 

 

 

command. Communications are

 

 

 

 

 

possible on three network levels,

 

 

 

 

 

including the local network.

 

 

 

 

 

10: Com-

01: Command

Command data

The command is longer than

Check the command format of

mand format

too long

 

the max. permissible length.

the command and set it correctly.

error

 

 

 

 

Be sure broadcast transmissions

 

 

 

 

 

don’t exceed 1,473 bytes.

 

 

 

 

 

 

02: Command

Command data

The command is shorter than

Check the command format of

 

too short

 

min. permissible length.

the command and set it correctly.

 

 

 

 

 

 

03: Element-data

Command data

The designated number of data

Check the number of items and

 

mismatch

 

items differs from the actual

the data, and make sure that

 

 

 

 

number in the command data.

they agree.

 

 

 

 

 

 

05: Header

Command data

Data for another node on the

Check the header parameters in

 

parameter error

 

same network was received

the command data and be sure

 

 

 

 

from the network.

the correct command format is

 

 

 

 

 

being used.

 

 

 

 

An attempt was made to send

 

 

 

 

 

 

 

 

 

response data for a broadcast

 

 

 

 

 

address.

 

 

 

 

 

 

 

224

Page 249
Image 249
Omron CS1W-ETN21 operation manual 224