Omron CS1W-ETN21 operation manual 204

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 229
Image 229

Error Log

 

 

Section 8-3

 

 

 

 

 

 

Error

Meaning

Detailed error code

Correction

EE-

code

 

 

 

 

PROM

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

0103

Resend count exceeded (send

Commands

 

Check transceiver at remote node.

---

 

failed)

Bit 15:

OFF

 

 

 

 

Bits 08 to 14: SNA

 

 

0105

Node address setting error (send

Set the IP address correctly.

---

Bits 00 to 07: SA1

 

failed)

 

 

 

Responses

 

 

 

 

 

 

 

 

0107

Remote node not in network (send

ON

Check the connection to the

---

 

failed)

Bit 15:

remote node.

 

 

Bits 08 to 14: DNA

 

 

 

 

 

0108

No Unit with specified unit

Check the unit address at the

---

Bits 00 to 07: DA1

 

address (send failed)

 

 

remote node.

 

010B

CPU Unit error (send failed)

 

 

Troubleshoot the error in the CPU

---

 

 

 

 

Unit using the PLC operation

 

 

 

 

 

manual.

 

 

 

 

 

 

 

010D

Destination address not in routing

 

 

Set the destination address in the

---

 

tables (send failed)

 

 

routing tables.

 

 

 

 

 

 

 

010E

No routing table entry (send

 

 

Set the local node, remote node,

---

 

failed)

 

 

and relay nodes in the routing

 

 

 

 

 

tables.

 

 

 

 

 

 

 

010F

Routing table error (send failed)

 

 

Create the routing tables correctly.

---

 

 

 

 

 

 

0110

Too many relay points (send

 

 

Reconstruct the network or cor-

---

 

failed)

 

 

rect the routing tables so that

 

 

 

 

 

commands are sent to within a 3-

 

 

 

 

 

level network range.

 

 

 

 

 

 

 

0111

Command too long (send failed)

 

 

Check the command format and

---

 

 

 

 

set the correct command data.

 

 

 

 

 

 

 

0112

Header error (send failed)

 

 

Check the command format and

---

 

 

 

 

set the correct command data.

 

 

 

 

 

 

 

0117

Internal buffers full; packet dis-

 

 

Change the network so that traffic

---

 

carded

 

 

is not concentrated.

 

 

 

 

 

 

 

0118

Illegal packet discarded

 

 

Check for nodes sending illegal

---

 

 

 

 

packets.

 

 

 

 

 

 

 

0119

Local node busy (send failed)

 

 

Change the network so that traffic

---

 

 

 

 

is not concentrated.

 

 

 

 

 

 

 

0120

Unexpected routing error

 

 

Check the routing tables.

---

 

 

 

 

 

 

0121

No setting in IP address table;

 

 

Set the remote node in the IP

---

 

packet discarded

 

 

address table.

 

 

 

 

 

 

 

0122

Service not supported in current

 

 

Select the IP address table or

---

 

mode; packet discarded

 

 

both methods for the address con-

 

 

 

 

 

version method.

 

 

 

 

 

 

 

0123

Internal send buffer full; packet

 

 

Change the network so that traffic

---

 

discarded

 

 

is not concentrated.

 

 

 

 

 

 

 

0124

Maximum frame size exceeded;

 

 

Reduce the size of events.

---

 

routing failed

 

 

 

 

 

 

 

 

 

 

021A

Logic error in setting table

00

01: Data link

Recreate the data specified by the

Saved

 

 

 

table

2nd byte of the detailed error

 

 

 

 

02: Network

code.

 

 

 

 

 

 

 

 

 

parameters

 

 

 

 

 

03: Routing

 

 

 

 

 

tables

 

 

 

 

 

04: Unit

 

 

 

 

 

Setup

 

 

 

 

 

05: CPU Bus

 

 

 

 

 

Unit Words

 

 

 

 

 

(CIO/DM)

 

 

 

 

 

 

 

 

204

Page 229
Image 229
Omron CS1W-ETN21 operation manual 204