Omron CS1W-ETN21 Error Log, Logged Errors, Following errors are recorded in the error log

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 227
Image 227

Error Log

 

 

 

Section 8-3

 

 

 

 

 

 

Bit

Error

 

Status

Manipulated by

Unit operation

 

 

 

 

 

 

5

DNS server error

 

ON

Unit

ON when the following errors occur during DNS server

 

 

 

 

 

operation:

 

 

 

 

 

• An illegal server IP address is set.

 

 

 

 

 

• A timeout occurs during communications with the

 

 

 

 

 

server.

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF when DNS server operation is normal.

 

 

 

 

 

 

6

Routing table error

 

ON

Unit

ON if the routing table information is incorrect.

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF when the routing table is normal.

 

 

 

 

 

 

7 to 10

(Not used.)

 

---

---

---

 

 

 

 

 

 

11

SNTP server error

 

ON

Unit

ON when the following errors occur during SNTP server

 

 

 

 

 

operation:

 

 

 

 

 

• An illegal server IP address or host name is set.

 

 

 

 

 

• A timeout occurs during communications with the

 

 

 

 

 

server.

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF when SNTP server operation is normal.

 

 

 

 

 

 

12

SMTP server error

 

ON

Unit

ON when the following errors occur during SMTP server

 

 

 

 

 

operation:

 

 

 

 

 

• An illegal server IP address or host name is set.

 

 

 

 

 

• A timeout occurs during communications with the

 

 

 

 

 

server.

 

 

 

 

 

• The verification time from the server has expired (when

 

 

 

 

 

POP before SMTP is set).

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF when SMTP server operation is normal.

 

 

 

 

 

 

13

POP server error

 

ON

Unit

ON when the following errors occur during POP server

 

 

 

 

 

operation:

 

 

 

 

 

• An illegal server IP address or host name is set.

 

 

 

 

 

• A server verification error (user name or password)

 

 

 

 

 

occurs.

 

 

 

 

 

• A timeout occurs during communications with the

 

 

 

 

 

server.

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF when use of the POP server is normal.

 

 

 

 

 

 

14

Address disagreement

 

ON

Unit

ON if the remote IP address is set to automatic genera-

 

 

 

 

 

tion but the local IP address host number and FINS

 

 

 

 

 

node address do not agree.

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF under all other circumstances.

 

 

 

 

 

 

15

EEPROM error

 

ON

Unit

ON if an error has occurred in the EEPROM memory.

 

 

 

 

 

 

 

 

 

OFF

Unit

OFF when the EEPROM memory is normal.

 

 

 

 

 

 

8-3

Error Log

 

 

 

 

 

 

The Ethernet Unit provides an error log that records errors that have occurred

 

 

during Ethernet Unit operation. The contents of the error log can be read or

 

 

cleared from a Programming Device, such as the CX-Programmer,or it can

 

 

be read or cleared using FINS commands from a workstation or computer.

 

 

(See 7-3-7 ERROR LOG READ and 7-3-8 ERROR LOG CLEAR).

Logged Errors

The following errors are recorded in the error log.

Errors in network operation

Errors in data transfers

Error in the CPU Unit

202

Page 227
Image 227
Omron CS1W-ETN21 operation manual Error Log, Logged Errors, Following errors are recorded in the error log