Main code

Sub-code

Check point

Probable cause

Remedy

 

 

 

 

 

11: Parame-

00: Parameter

Parameters in

The parameters in the com-

Check the parameters.

ter error

error

command data

mand data are incorrect.

 

 

 

 

The UDP/TCP socket number

Be sure the socket number is

 

 

 

was not within the proper

between 1 and 8.

 

 

 

range.

Set the Local UDP port number

 

 

 

The local UDP port number

 

 

 

correctly.

 

 

 

might be set to 0.

 

 

 

 

 

 

 

01: No area

Memory area

A correct memory area code

Check the command’s memory

 

specification

code in command

has not been used or EM Area

area code in the Results Storage

 

 

data

is not available.

Area and set the appropriate

 

 

 

 

code.

 

 

 

 

 

 

03: Address

First word

The first word is in an inacces-

Set a first word that is in an

 

specification out

address in com-

sible area or the bit number is

accessible area. The bit number

 

of range

mand data

not 00.

must be 00 for Ethernet Units.

 

 

 

 

 

 

04: Address

Command data

The address set in the com-

Correct the address in the com-

 

range exceeded

 

mand is not correct.

mand data, being sure that the

 

 

 

 

start address plus the number of

 

 

 

 

words does not exceed accessi-

 

 

 

 

ble memory.

 

 

 

 

 

 

0B: Response

Command data

The response frame is too

Correct the number of data ele-

 

too long

 

long.

ments or other parameters in the

 

 

 

 

command data for which the

 

 

 

 

response is being returned.

 

 

 

 

 

 

0C: Parameter

Parameters in

Parameters are set incorrectly

Check the command data and

 

error

command data

in the command data.

correct any parameters that are

 

 

 

 

incorrect.

 

 

 

 

 

21: Cannot

08: Cannot

IP address con-

With respect to a FINS node

Referring to SECTION 5 Deter-

write

change

version method

address that could not be

mining IP Addresses, correct the

 

 

 

dynamically changed, a FINS

relationships between IP

 

 

 

message was received from an

addresses and FINS node

 

 

 

IP address that differed from

addresses.

 

 

 

the Unit Setup.

 