Omron CS1W-ETN21 operation manual 175

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 200
Image 200

Command/Response Reference

Section 7-3

Response Block

27 11

Command Response

code code

Results Storage Format

Response Local port

code number

Parameters

Socket Option (Command) The socket option is specified in one byte.

7

 

 

0 Bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep-alive specification 0: Keep-alive disabled

1: Keep-alive enabled

TCP Socket Number (Command)

Results Storage Area (Command)

Local TCP Port Number

(Command, Results

Storage Area)

Remote IP Address (Command)

Remote Port Number (Command)

The TCP socket number to be opened specified as 1 byte between 1 and 8.

The area in which the results of the command execution are stored. The first byte specifies the memory area and data type (variable type). The 2nd to 4th bytes specify the beginning address of the results storage area. Refer to page 158 for details about the variable types and addresses that can be spec- ified.

The TCP port number for communications with the socket is specified as 2 bytes. An available TCP port number is automatically assigned if 0 is speci- fied.

The TCP port numbers allocated to the open socket are stored in the Results Storage Area.

The following ports used for the Ethernet Unit's communications services can- not be specified.

TCP port No. used for FTP server (Default: 20, 21)

TCP port No. used for DNS server access (Default: 53)

TCP port No. used for SMTP server access (Default: 25)

TCP port No. used for POP server access (Default: 110)

TCP port No. used for HTTP server (Default: 80)

Specify the remote node’s IP address (must be non-zero) in hexadecimal.

Specify the remote TCP port number (must be non-zero).

175