Omron CS1W-ETN21 operation manual Troubleshooting with Response Codes, Controller, Status Read

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 248
Image 248

Troubleshooting with Response Codes

Section 8-5

8-5 Troubleshooting with Response Codes

You can troubleshoot the errors in FINS communications from the response codes when the SEND(090), RECV(098), or CMND(490) instructions have been used. For the storage areas of the response codes refer to information on page 141 under 6-6-4 Writing Programs.

The table below lists response codes (main and sub-codes) returned after execution of FINS commands, the probable cause of errors, and recom- mended remedies. The response codes provided here are for the Ethernet Unit. Refer to the FINS Command Reference Manual (W227) or the operation manuals for the relevant Unit for further information on response codes.

The 6th, 7th, and 15th bits of the response codes have specific functions. The 6th bit will be ON when a non-fatal error has occurred in the PC at the remote node; the 7th bit will be ON when a fatal error has occurred in the PC at the remote node; and the 15th bit will be ON when a network relay error has occurred. Refer to information given after the following table for more informa- tion on relay errors.

 

 

 

 

First byte

 

 

 

 

 

Second byte

 

 

 

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

 

 

Ma

in response code (MR

ES)

 

 

Sub-response code (SRE

S)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1:PLC fatal error flag

1:Relay error flag

1: PLC non-fatal error flag

Main code

Sub-code

Check point

Probable cause

Remedy

 

 

 

 

 

 

00: Normal

00

 

---

---

---

completion

 

 

 

 

 

 

 

 

 

 

 

01: Local

03: Local node

---

Send error in local node was

Reduce the load (traffic) on the

node error

send error

 

caused by lack of available

Ethernet Unit. Check your user

 

 

 

 

space in internal buffers.

applications.

 

 

 

 

 

 

 

05: Node address

Local IP address

The network cannot be

Correct the local IP address.

 

setting error

 

accessed because the IP

 

 

 

 

 

address setting is not correct.

 

 

 

 

 

 

 

 

07: Local node

System load

The internal buffers are full

Correct the user application to

 

busy, cannot

 

because there is too much traf-

reduce traffic at the Ethernet

 

send

 

fic at the local node, preventing

Unit.

 

 

 

 

data from being sent.

 

 

 

 

 

 

 

02: Remote

01: Remote node

IP address table,

IP address of remote node not

Set IP address of remote node

node error

not in network

IP router table

set correctly in IP address table

into IP address table and, if inter-

 

 

 

 

or IP router table.

network transmission is required,

 

 

 

 

 

into the IP router table.

 

 

 

 

 

 

 

02: No such Unit

Control data in

No node with the specified unit

Check the remote node’s unit

 

 

 

instruction

address.

address and make sure the cor-

 

 

 

 

 

rect one is being used in the con-

 

 

 

 

 

trol data.

 

 

 

 

 

 

 

05: Response

Response to

Message packet was corrupted

Check the protocol and controller

 

timeout

CONTROLLER

by transmission error.

status by reading them with FINS

 

 

 

STATUS READ

 

commands. Increase the num-

 

 

 

and PROTOCOL

 

ber of transmit retry attempts.

 

 

 

STATUS READ

 

 

 

 

 

FINS command

 

 

 

 

 

 

 

 

 

 

 

Control data in

Response time-out, response

Increase the value for the

 

 

 

instruction

watchdog timer interval too

response monitor time in the

 

 

 

 

short.

control data.

 

 

 

 

 

 

 

 

 

Read error log

The transmission frame may

Read out the error log and cor-

 

 

 

 

be corrupted or the internal

rect as required.

 

 

 

 

reception buffer full.

 

223

Page 248
Image 248
Omron CS1W-ETN21 Troubleshooting with Response Codes, Main code Sub-code Check point Probable cause Remedy, Controller