Omron CS1W-ETN21 operation manual Controller Status Read

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 186
Image 186

Command/Response Reference

Section 7-3

Ethernet Address (Response)

FFINS/TCP Port Number Setting

0:Default (9600)

1:Unit Setup value

Baud Rate setting

0:Automatic detection

1:10Base-T

SNTP Server Specification Method

0:IP address

1:Host name

SMTP Server Specification Method

0:IP address

1:Host name

POP Server Specification Method

0:IP address

1:Host name

System Setup Format

 

 

Bit address

 

 

Format classification

 

 

 

 

 

 

 

15

 

14

13

 

12

 

 

 

 

 

 

 

 

0

0

 

0

0

 

ETN11 mode

 

 

 

 

 

 

 

0

0

 

0

1

 

ETN21 mode

 

 

 

 

 

 

 

Other

 

 

 

 

 

Reserved

 

 

 

 

 

 

 

The Ethernet address of the Ethernet Unit is returned. The Ethernet address is the address marked on the label on the side of the Ethernet Unit.

Response Codes

Response code

Description

 

 

0000

Normal

 

 

1001

Command too large

 

 

7-3-3 CONTROLLER STATUS READ

Reads the controller status.

Command Block

06 01

Command code

Response Block

06 01

2 byte

4 byte

4 byte

4 byte

4 byte

4 byte

Command

Response

Error flags Total number

Total number

Total number

Total number

Total number

code

code

of

of

of

of

of

 

 

packets received

receive errors

packets sent

errors sent

send collisions

161

Page 186
Image 186
Omron CS1W-ETN21 operation manual Controller Status Read