Omron CS1W-ETN21 operation manual Error Log Error Codes, Error Log Table

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 228
Image 228

 

Error Log

Section 8-3

Error Log Table

Each error is recorded as one record in an error log table. Up to 64 records

 

 

can be saved. If more than 64 errors occur, the oldest errors will be deleted

 

 

from the error log and the most recent error will be recorded.

 

 

The following information is recorded in the error log table.

 

 

• Main error code (See table later in this section.)

 

 

• Detailed error code (See table later in this section.)

 

 

• Time stamp (from the clock in the CPU Unit)

Error Log Location

FINS Commands for Error Logs

When an error is detected, the error codes and time stamp are recorded in the error log in RAM inside the Ethernet Unit. Serious errors are also recorded in EEPROM. The maximum number of errors that can be saved to EEPROM is 64 for the CS Series and 32 for the CJ Series. The errors recorded in EEPROM will be saved even if the Unit is restarted or power is turned OFF. When the Ethernet Unit is started, the contents of the error log in EEPROM is copied to RAM.

When a FINS command is used to read the error log, the log held in RAM is read. When a FINS command is used to clear the error log, the logs held in both RAM and EEPROM are cleared.

The following FINS commands can be used to read or clear the error log. Refer to SECTION 7 FINS Commands Addressed to Ethernet Units.

Command

Function

code

 

 

 

MRC SRC

 

2102 ERROR LOG READ

03 ERROR LOG CLEAR

8-3-1

Error Log Error Codes

 

 

 

 

The error codes are described in the following table. The detailed error code

 

will provide detailed information on an error.

 

 

 

 

 

 

 

Error

Meaning

Detailed error code

Correction

EE-

code

 

 

 

 

PROM

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

0001

Watchdog timer error in CPU Unit

00

00

Replace the CPU Unit.

Saved

 

 

 

 

 

 

0002

CPU Unit service monitor error

Monitor time (ms)

Check the operating environment.

Saved

 

 

 

 

 

0006

Other CPU error

Bit 11: Unit not in Registered

Create the I/O tables.

Saved

 

 

I/O Tables

 

 

 

 

 

Other bits are reserved for

 

 

 

 

system use.

 

 

 

 

 

 

 

 

 

000F

CPU Unit initialization error

00

00

Replace the CPU Unit.

Saved

 

 

 

 

 

 

0010

Insufficient System Setup Area

00

00

Reduce the number of CPU Bus

Saved

 

 

 

 

Units.

 

 

 

 

 

 

 

0011

Event timed out

MRC

SRC

Replace the CPU Unit.

Saved

 

 

 

 

 

 

0012

CPU Unit memory error

01: Read

03: Routing

01: Recreate the data specified by

Saved

 

 

error

table

the 2nd byte of the detailed error

 

 

 

02: Write

04: Setup

code.

 

 

 

 

 

 

 

error

error

02: Clear memory using proce-

 

 

 

 

05: CPU Bus

dure in the PLC operation manual.

 

 

 

 

 

 

 

 

 

Unit Words

 

 

 

 

 

(CIO/DM)

 

 

 

 

 

 

 

 

0013

CPU Unit protected

00

00

Remove protection from CPU Unit

Saved

 

 

 

 

memory.

 

 

 

 

 

 

 

203

Page 228
Image 228
Omron CS1W-ETN21 operation manual Error Log Error Codes, Error Log Table, Error Log Location Fins Commands for Error Logs