Command/Response Reference

Section 7-3

IP Address Table Records (Command)

Precautions

Response Codes

Specify the IP address table records. The number of records specified must be provided. The total number of bytes in the IP address table records is cal- culated as the number of records 6 bytes/record. The configuration of the 6 bytes of data in each record is as shown in the following diagram.

1

6 bytes

00

 

FINS node

IP address

number

 

FINS Node Address

Node address for communications via the FINS command (hexadecimal).

IP Address

IP address used by TCP/IP protocol (hexadecimal).

The new I/O address table records will not be effective until the PC is restarted or the Ethernet Unit is reset.

An error response will be returned if the IP address conversion method in the system mode settings is set for automatic generation.

Response code

Description

 

 

0000

Normal (echo reply received from the remote node)

 

 

1001

Command too large

 

 

1002

Command too small

 

 

1003

The number of records specified does not match the sent data

 

length.

 

 

110C

The number of records is not between 0 and 32.

 

The FINS node address is not between 1 and 126

 

The IP address is 0.

 

 

2307

IP address conversion method is set for automatic generation.

 

 

7-3-22 IP ADDRESS WRITE

Write the local IP address and the subnet mask in the CPU Bus Unit System

Setup.

Command Block

27

57

 

 

Command

IP address

Subnet mask

code

 

 

Response Block

27 57

Command Response

code code

185

Page 210
Image 210