3-2 FINS/TCP

FINS/TCP Connection Setup

Item

Contents

Default

No.

Shows the connection number. This is a network API

 

 

used when TCP is used for the FINS communica-

 

 

tions service. It corresponds to a socket in the socket

 

 

services. Up to 16 can be used at a time, and they

 

 

are identified by connection numbers 1 to 16. The

 

 

Ethernet Unit can thus simultaneously execute the

 

 

FINS communications service by TCP with up to 16

 

 

remote nodes.

 

 

 

 

Use IP address

When this option is selected, if the Ethernet Unit is

Not pro-

to protect

set for use as a server, and if a connection number

tected

 

other than 0.0.0.0 is set for a destination IP address,

 

 

any connection request from other than the number

 

 

set for that IP address will be denied.

 

 

Select this option to prevent faulty operation (by

 

 

FINS commands) from specific nodes from affecting

 

 

the PLC.

 

 

 

 

64