IP Addresses in FINS Communications

Section 5-2

5-2 IP Addresses in FINS Communications

5-2-1 Specifying Nodes in FINS Communications Services

With FINS communications services on an Ethernet network, IP addresses, UDP port numbers, and TCP port numbers are paired with FINS node addresses to specify nodes on the network.

Application level

FINS

 

Node number

 

 

 

 

 

Transport level

UDP

UDP port

TCP

TCP port

 

 

 

 

 

number

 

number

Internet level

IP

 

IP address

Must be allocated.

 

 

 

 

Physical level

Ethernet

 

 

Automatically allocated

Ethernet address

 

 

 

 

Note Use the “Node No.” rotary switch on the front of the Ethernet Unit to set the FINS node address.

Allocating Addresses to Ethernet Units

Ethernet Unit FINS Message Reception

The IP address, FINS/UDP port number, and FINS/TCP port number set for the Ethernet Unit are mainly used when receiving FINS communications mes- sages.

Application level

FINS

Node number

 

 

 

 

Transport level

UDP

UDP port

TCP

TCP port

 

 

number

 

number

Internet level

IP

 

IP address

 

 

 

 

 

Physical level

Ethernet

 

 

 

 

Ethernet address

Receives communications data

 

 

 

 

 

 

 

 

conforming to Ethernet address,

 

 

 

 

IP address, UDP port number,

 

 

 

 

and FINS node number.

Ethernet V2

IP

UDP

FINS header

FINS data

• Ethernet address:

A fixed number is assigned to each Ethernet Unit

 

and it cannot be changed.

• IP address:

Either use the default IP address

 

(192.168.250.FINS_node number), or set the

 

address in the word allocated in the DM Area or

 

in the Unit Setup from the CX-Programmer.

FINS/UDP port number: Either use the default FINS/UDP port number (9600) or set the number using the CX-Program- mer's Unit Setup.

FINS/TCP port number: Either use the default FINS/TCP port number (9600) or set the number using the CX-Program- mer's Unit Setup.

• FINS node address:

Set the number using the NODE NO. rotary

 

switch on the front of the Ethernet Unit.