Omron CS1W-ETN21 operation manual Using Fins Applications, CX-Programmer CX-Server

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 151
Image 151

Using FINS Applications

Section 6-5

6-5 Using FINS Applications

6-5-1 CX-Programmer (CX-Server)

The following examples show how to connect online from a CX-Programmer on an Ethernet network to a PLC on the Ethernet network.

System Configuration Example 1: No Routing

In this example, an online connection is made by FINS/UDP to a PLC on an

Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-

Integrator connected to the Ethernet network.

Conditions

FINS/UDP method

IP address conversion: Automatic generation method (dynamic)

CX-Programmer/CX-Integrator

Node number: 1

Ethernet Unit

IP address: 192.168.250.1

 

IP address conversion: Automatic generation method (dynamic)

Ethernet port

Ethernet (Network address: None)

FINS/UDP method

Ethernet Unit node number: 2

Ethernet Unit IP address: 192.168.250.2

Target: PLC1

CX-Programmer's Change PLC Dialog Box

Settings for target PLC (PLC1)'s Change PLC Dialog Box

Setting

 

 

 

 

PLC name

 

 

PLC1

 

 

 

 

Network classification

 

 

Ethernet

 

 

 

 

Network Tab

FINS transmission source address

0

 

 

 

 

 

FINS destination

Network number

0

 

 

 

 

 

 

Node address

2

 

 

 

 

 

Frame length

 

2,000 bytes

 

 

 

 

Response monitor time

2 seconds

 

 

 

Driver Tab

Workstation node address

1

 

 

 

 

Automatic generation method

Not selected

 

 

 

 

 

IP address

 

192.168.250.2

 

 

 

(Ethernet Unit IP

 

 

 

address)

 

 

 

 

 

Port number

 

9600

 

 

 

 

126

Page 151
Image 151
Omron CS1W-ETN21 Using Fins Applications, CX-Programmer CX-Server, System Configuration Example 1 No Routing