Omron CS1W-ETN21 operation manual Parameters, Communications Type, Cio

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 183
Image 183

Socket Applications

 

 

 

Section 7-2

Parameters

 

 

Specifies the parameters for the command code. Parameters depend on the

 

 

 

 

command being executed; for details, refer to the following pages.

 

7-2-2

PLC Memory Areas

 

 

 

 

 

 

 

 

The memory areas of the PLC that can be specified for results storage when

 

 

 

 

executing commands from the PC are listed in the table below. The Variable

 

 

 

 

type is set in the first byte of the results storage area. The remaining three

 

 

 

 

bytes contain the address for communications.

 

 

 

 

 

 

Addresses in the Addresses for communications column are not the same as

 

 

 

 

the actual memory addresses.

 

 

 

 

 

 

 

 

 

 

 

 

Memory

 

Data type

 

Word addresses

Addresses for

Variable

Bytes

area

 

 

 

 

 

communications

type

 

Bit Areas

Current

 

CIO

 

CIO 0000 to CIO 6143

000000 to 17FF00

B0 (80)*

2

 

value of

 

 

 

 

 

 

 

 

 

HR

 

H000 to H511

000000 to 01FF00

B2

 

 

word

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

A448 to A959

01C000 to 03BF00

B3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DM Area

 

 

DM

 

D00000 to D32767

000000 to 7FFF00

82

2

 

 

 

 

 

 

 

 

 

EM Area

 

 

Bank 0

 

E0_E00000 to E0_E32767

000000 to 7FFF00

A0 (90)*

2

 

 

 

 

 

 

 

 

 

 

 

 

Bank 1

 

E1_E00000 to E1_E32767

000000 to 7FFF00

A1 (91)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 2

 

E2_E00000 to E2_E32767

000000 to 7FFF00

A2 (92)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 3

 

E3_E00000 to E3_E32767

000000 to 7FFF00

A3 (93)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 4

 

E4_E00000 to E4_E32767

000000 to 7FFF00

A4 (94)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 5

 

E5_E00000 to E5_E32767

000000 to 7FFF00

A5 (95)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 6

 

E6_E00000 to E6_E32767

000000 to 7FFF00

A6 (96)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 7

 

E7_E00000 to E7_E32767

000000 to 7FFF00

A7 (97)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Bank 8

 

E8_E00000 to E8_E32767

000000 to 7FFF00

A8

2

 

 

 

 

 

 

 

 

 

 

 

 

Bank 9

 

E9_E00000 to E9_E32767

000000 to 7FFF00

A9

2

 

 

 

 

 

 

 

 

 

 

 

 

Bank A

 

EA_E00000 to EA_E32767

000000 to 7FFF00

AA

2

 

 

 

 

 

 

 

 

 

 

 

 

Bank B

 

EB_E00000 to EB_E32767

000000 to 7FFF00

AB

2

 

 

 

 

 

 

 

 

 

 

 

 

Bank C

 

EC_E00000 to EC_E32767

000000 to 7FFF00

AC

2

 

 

 

 

 

 

 

 

 

 

 

Current bank

E00000 to E32767

000000 to 7FFF00

98

2

Note The variable types (area designations) given in parentheses can also be used, allowing CV-series or CVM1 programs to be more easily corrected for use with CS/CJ-series PLCs.

Word and Bit Addresses Three bytes of data are used to express data memory addresses of PLCs. The most significant two bytes give the word address and the least significant byte gives the bit number between 00 and 15.

The word address combined with the bit number expresses the bit address. The bit number is always 00 because Ethernet Units can handle only word data, i.e., individual bits cannot be addressed.

Specifies the bit position between 00 and 0F (0 to 15) for bit data.

Specifies the address of the corresponding word.

Variable type

Word addresses for specific memory area words can be calculated by con- verting the normal decimal word address to hexadecimal and adding it to the first word in the Addresses for communications column in the above table. For example, the address for communications for D00200 would be 0000 (from above table) plus C8 (decimal 200 converted to hexadecimal), or 00C8.

158

Page 183
Image 183
Omron CS1W-ETN21 operation manual Parameters, Communications Type, Cio