Command/Response Reference

Section 7-3

Response Codes

 

 

 

 

 

Response code

Description

 

 

 

 

0000

Normal

 

 

 

 

0105

Local IP address setting error

 

 

 

 

0302

CPU Unit error; execution not possible.

 

 

 

 

1001

Command too large

 

 

 

 

1002

Command too small

 

 

 

 

1100

TCP socket number is out of range.

 

 

Remote IP address or the remote TCP port number is 0.

 

 

 

 

1101

The variable type for the results storage area is out of range.

 

 

 

 

1103

Non-zero bit address specified for the results storage area.

 

 

 

 

220F

The specified socket (connection) is already open or is being

 

 

opened.

 

 

 

 

2211

High traffic at Unit; cannot execute service.

 

 

 

Results Storage Area Response Codes

 

 

 

 

 

Response code

Description

 

 

 

 

0000

Normal

 

 

 

 

000D

A parameter error occurred at the remote IP address

 

 

(EACCES).

 

 

 

 

003E

Internal buffer cannot be reserved due to high receive load

 

 

(ENOBUFS).

 

 

 

 

0042 (see note)

An error occurred (EMSGSIZE).

 

 

 

 

0044

Received ICMP data (ENOPROTOOPT).

 

 

 

 

0045

Local socket closed (ECONNABORTED).

 

 

 

 

0049

Duplicated port numbers (EADDRINUSE).

 

 

 

 

004A

An error occurred (ECONNREFUSED).

 

 

Passive remote is not available.

 

 

 

 

004B (see note)

A communication error occurred with the remote node

 

 

(ECONNRESET).

 

 

 

 

004C

A parameter error occurred at the remote IP address (EAD-

 

 

DRNOTAVAIL).

 

 

A parameter was specified incorrectly.

 

 

An attempt was made to actively open local TCP port.

 

 

 

 

004E

A parameter error occurred at the remote IP address

 

 

(ENETUNREACH). No network number in IP router table or

 

 

incorrect router setting.

 

 

 

 

0051

A parameter error occurred at the remote IP address

 

 

(EHOSTUNREACH). Incorrect router setting.

 

 

 

 

0053

A communication error occurred with the remote node

 

 

(ETIMEDOUT). No remote exists.

 

 

 

 

0081

Socket was closed during opening procedure.

 

 

 

Note These errors occur only in large multilayered networks.