Omron CS1W-ETN21 Routing Table Setting Examples, Example 2 Three Interconnected Networks

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 149
Image 149

Creating Routing Tables

Section 6-4

6-4-3 Routing Table Setting Examples

Example 1: Local Network Table for a PLC With Multiple Units Mounted

This example shows the local network table settings for a PLC to which multi- ple CPU Bus Units are mounted.

Ethernet network

(Network #A)

Controller Link network

(Network #B)

 

 

E

C

C

P

PS: Power Supply Unit

 

 

CPU: CPU Unit

 

 

T

L

P

S

 

 

N

K

U

 

ETN: Ethernet Unit

 

 

 

 

 

 

CLK: Controller Link Unit

 

 

 

 

 

 

Unit #a Unit #b

Local Network Table

No.

Local

CPU Bus

 

network

Unit

1

A

a

2

B

b

 

 

 

Example 2: Three Interconnected Networks

This example shows the relay network table settings for three different inter- connected networks.

Network #A

Network #B

Network #C

PLC #1

Node #a

PLC #2 Node #b Node #c

PLC #3

Node #d

PLC #4 Node #e Node #f

PLC #5

Node #g

Relay Network Table

No.

End

Relay

Node

network

network

 

 

 

 

 

 

 

 

1

B

A

b

2

C

A

b

 

 

 

 

 

 

 

 

1

C

B

e

 

 

 

 

 

 

 

 

1

A

B

c

2

C

B

e

 

 

 

 

 

 

 

 

1

A

B

c

 

 

 

 

 

 

 

 

1

A

C

f

2

B

C

f

 

 

 

 

In the table for PLC #3, for example, if network #A is taken as the end net- work, then network #B becomes the relay network and node #c becomes the relay node. If network #C is taken as the end network, then network #B still becomes the relay network and node #e becomes the relay node.

124

Page 149
Image 149