Omron CS1W-ETN21 Auxiliary Area Data, Area of PLC memory that are related to the Ethernet Unit

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 115
Image 115

Auxiliary Area DataSection 4-3

4-3

Auxiliary Area Data

 

 

 

The following table and descriptions cover the words and bits in the Auxiliary

 

 

Area of PLC memory that are related to the Ethernet Unit.

Read-only Bits/Words

 

 

 

 

 

 

 

Word(s)

Bit(s)

Name

Function

Settings

 

 

 

 

 

A202

A20200 to

Communications

Bits A20200 to A20207 turn ON when a network

0: Network communi-

 

A20207

Port Enabled Flags

instruction (SEND, RECV, CMND, or PMCR) can be

cations running

 

 

 

executed with the corresponding port number. Bits

1: No network com-

 

 

 

00 to 07 correspond to communications ports 0 to 7.

 

 

 

munications running

 

 

 

 

 

A203 to

---

Communications

These words contain the completion codes for the

0000: No error

A210

 

Port Completion

corresponding port numbers when network

Not 0000: Error code

 

 

Codes

instructions (SEND, RECV, CMND, or PMCR) have

 

 

 

 

 

 

been executed. Words A203 to A210 correspond to

 

 

 

 

communications ports 0 to 7.

 

 

 

 

 

 

A219

A21900 to

Communications

Bits A21900 to A21907 turn ON when an error

0: Normal end

 

A21907

Port Error Flags

occurred during execution of a network instruction

1: Error end

 

 

 

(SEND, RECV, CMND, or PMCR). Bits 00 to 07

 

 

 

 

 

 

 

correspond to communications ports 0 to 7.

 

 

 

 

 

 

A302

A30200 to

CPU Bus Unit

Bits A30200 through A30215 turn ON while the

0: Not initializing

 

A30215

Initializing Flags

corresponding CPU Bus Units (Units #0 through

1: Initializing (System

 

 

 

#15, respectively) are initializing. The bits will turn

 

 

 

will automatically turn

 

 

 

ON either when power is turned ON or when a CPU

 

 

 

the flag OFF when ini-

 

 

 

Bus Unit Restart Bit (A50100 to A50115) is turned

tialization has been

 

 

 

ON.

 

 

 

completed.)

 

 

 

 

 

 

 

 

 

A402

A40203

CPU Bus Unit Set-

Bit A40203 is turned ON when the CPU Bus Units

0: No setting error

 

 

ting Error Flag

actually installed differ from the Units registered in

1: Setting error

 

 

(Non-fatal error)

the I/O tables. The ERR/ALM indicator on the front

 

 

 

 

 

 

of the CPU Unit will flash, but CPU operation will

 

 

 

 

continue.

 

 

 

 

The unit number of the CPU Bus Unit involved is

 

 

 

 

stored in word A427.

 

 

 

 

 

 

 

A40207

CPU Bus Unit Error

Bit A40207 is turned ON when an error occurs

0: No unit number

 

 

Flag

during the transmission of data between the CPU

error

 

 

(Non-fatal error)

and CPU Bus Units. The ERR/ALM indicator on the

1: Unit number error

 

 

 

front of the CPU Unit will flash, but CPU operation

 

 

 

 

will continue. The Unit where the error occurred will

 

 

 

 

stop.

 

 

 

 

The unit number of the CPU Bus Unit involved is

 

 

 

 

stored in word A422.

 

 

 

 

 

 

A403

A40300 to

Memory Error

When a memory error occurs, the Memory Error

0: Normal

 

A40308

Location

Flag (A40115) is turned ON and one of the following

1: Error

 

 

 

flags is turned ON to indicate the memory area

 

 

 

 

where the error occurred.

 

 

 

 

A40300: User program

 

 

 

 

A40304: PLC Setup

 

 

 

 

A40305: Registered I/O Tables

 

 

 

 

A40307: Routing Table

 

 

 

 

A40308: CPU Bus Unit Settings

 

 

 

 

The ERR/ALM indicator on the front of the CPU Unit

 

 

 

 

will light and CPU operation will stop.

 

 

 

 

 

 

A410

A41000 to

CPU Bus Unit Num-

The Duplication Error Flag (A40113) and the

0: No duplication

 

A41015

ber Duplication

corresponding flag in A410 will be turned ON when

1: Duplication

 

 

Flags

a CPU Bus Unit’s unit number has been

 

 

 

 

 

 

duplicated. Bits 00 to 15 correspond to unit numbers

 

 

 

 

0 to F.

 

 

 

 

The ERR/ALM indicator on the front of the CPU Unit

 

 

 

 

will light and CPU operation will stop.

 

 

 

 

 

 

90

Page 115
Image 115
Omron CS1W-ETN21 Auxiliary Area Data, Area of PLC memory that are related to the Ethernet Unit, Read-only Bits/Words