Omron CS1W-ETN21 Following settings can be made for each connection number, Tion of Applications

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 90
Image 90

FINS/TCP

Section 3-2

 

The following settings can be made for each connection number.

 

 

 

 

 

 

 

Item

Contents

 

Default

 

 

 

 

 

 

FINS/TCP Mode

For each connection number, this setting specifies

 

Server

 

 

the Ethernet Unit for use as either a server or a cli-

 

 

 

 

ent.

 

 

 

 

• When the Ethernet Unit is used as a server:

 

 

 

 

The Ethernet Unit opens a connection with that

 

 

 

 

connection number and waits for service requests

 

 

 

 

(FINS commands) from clients. Connection num-

 

 

 

 

bers are used in ascending order and allocated to

 

 

 

 

clients in the order connections are made.

 

 

 

 

• When the Ethernet Unit is used as a client:

 

 

 

 

The Ethernet Unit establishes a connection with

 

 

 

 

the server set as the destination IP address. Once

 

 

 

 

the connection has been established, FINS/TCP is

 

 

 

 

used for FINS communications.

 

 

 

 

 

 

 

 

IP Address

• When the Ethernet Unit is used as a server:

 

0.0.0.0

 

 

If the option is selected to use IP addresses to pro-

 

 

 

 

tect, set the IP addresses as required at clients

 

 

 

 

from which connection is permitted. If not set for

 

 

 

 

those connections, the default setting of 0.0.0.0

 

 

 

 

can be used.

 

 

 

 

• When the Ethernet Unit is used as a client:

 

 

 

 

Set the IP address for the remote Ethernet Unit

 

 

 

 

(i.e., the server) that is to be connected by FINS/

 

 

 

 

TCP. It is required that an IP address be set for the

 

 

 

 

remote Ethernet Unit.

 

 

 

 

 

 

 

 

Auto allocated

If the client (normally a personal computer) applica-

 

From 239 to

 

FINS node

tion supports FINS/TCP, and if FINS node

 

254, for con-

 

 

addresses are not fixed, the client will take 0 as its

 

nection Nos.

 

 

node address. Then, when a FINS command

 

1 to 16

 

 

arrives, the number set here (from 239 to 254) will

 

 

 

 

automatically be allocated as the client's FINS node

 

 

 

 

address.

 

 

 

 

For details on automatic allocation of FINS node

 

 

 

 

addresses, refer to the Operation Manual Construc-

 

 

 

 

tion of Applications.

 

 

 

 

 

 

 

 

keep-alive

For each connection number, set whether or not the

 

Use

 

 

remote node connection check function is to be

 

 

 

 

used for the FINS/TCP server and client.

 

 

 

 

If the keep-alive box is checked here, then, when

 

 

 

 

the remote node goes without responding for longer

 

 

 

 

than the monitor time set in the Setup, the connec-

 

 

 

 

tion will be terminated. If a remote node turns OFF

 

 

 

 

without warning, the connection will remain open

 

 

 

 

indefinitely, so this option should be used whenever

 

 

 

 

possible.

 

 

 

 

 

 

 

For details, refer to SECTION 6 FINS Communications Service in the Opera- tion Manual Construction of Networks.

65

Page 90
Image 90
Omron CS1W-ETN21 operation manual Following settings can be made for each connection number, Tion of Applications