Troubleshooting with Response Codes

 

Section 8-5

 

 

 

 

 

Main code

Sub-code

Check point

Probable cause

Remedy

 

 

 

 

 

22: Status

0F: Service in

Socket status

The same socket service is

Use the socket status flag in PC

error (operat-

progress, cannot

area

already in progress at the

memory to be sure that socket

ing mode dis-

perform operation

 

specified socket number.

service has finished before start-

agreement)

 

 

 

ing services again.

 

 

 

 

 

 

10: Socket not

Socket status

The specified socket is not

Open the socket. For TCP sock-

 

open

area

open.

ets, be sure to wait until connec-

 

 

 

 

tion is made.

 

 

 

 

 

 

11: Local node

System load

The internal buffers are full

Correct the user application to

 

busy, cannot

 

because there is too much traf-

reduce traffic at the Ethernet

 

send

 

fic at the local node, preventing

Unit.

 

 

 

data from being sent.

 

 

 

 

 

 

 

20

Unit settings

The socket is not open for Sys-

Correct the settings for the Unit

 

 

 

tem Settings.

Setup, the FINS/TCP connection

 

 

 

 

number, the remote IP address,

 

21

 

The socket is not open

 

 

and the remote port number.

 

 

 

because of the remote node

 

 

 

 

 

 

 

conversion command for the

 

 

 

 

FINS/TCP connection.

 

 

 

 

 

 

 

22

 

The socket is reopening

 

 

 

 

because the connection to the

 

 

 

 

remote node has closed.

 

 

 

 

 

 

 

23

 

The socket is reopening

 

 

 

 

because of a reception error.

 

 

 

 

 

 

 

24

 

The socket is reopening

 

 

 

 

because of a transmission

 

 

 

 

error.

 

 

 

 

 

 

 

25

 

The socket is reopening

 

 

 

 

because RST received in

 

 

 

 

response to keep-alive.

 

 

 

 

 

 

 

26: FINS/TCP not

 

The socket is reopening

 

 

connected

 

because of no keep-alive

 

 

 

 

response.

 

 

 

 

 

 

 

30: Connection

Command data

A connection is already estab-

Correct the settings for the FINS/

 

not establish

 

lished with the specified

TCP connection number, the

 

 

 

remote node.

remote IP address, and the

 

 

 

 

remote port number.

 

 

 

 

 

 

31: Connection

Unit settings and

The specified connection num-

Correct the settings for the Unit

 

cannot be

command data

ber is not set as a FINS/TCP

Setup, the FINS/TCP connection

 

changed

 

client in the Unit Setup.

number, the remote IP address,

 

 

 

 

and the remote port number.

 

 

 

 

 

 

32: Service

Command data

While a remote node change

Correct the settings for the FINS/

 

stopped, cannot

 

was being processed for the

TCP connection number, the

 

perform operation

 

specified connection number, a

remote IP address, and the

 

 

 

request for a change was

remote port number.

 

 

 

received and the processing

 

 

 

 

was stopped.

 

 

 

 

 

 

23: Environ-

05: Parameter

Unit settings

IP address conversion failed.

Check the IP address and subnet

ment error (no

error

 

 

mask in the System Setup and

such Unit)

 

 

 

be sure that settings are correct.

 

 

 

 

 

 

07: Configuration

IP address con-

IP address conversion is set for

Check the mode settings in the

 

error

version in Unit

automatic conversion only.

System Setup. This error will be

 

 

settings

 

generated for the READ IP

 

 

 

 

ADDRESS TABLE command

 

 

 

 

only.

 

 

 

 

 