Omron CS1W-ETN21 operation manual Precautions, Remote IP address Remote TCP port Description

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 198
Image 198

Command/Response Reference

Section 7-3

TCP Socket Number (Command)

Results Storage Area (Command)

Local TCP Port Number (Command)

Timeout Value (Command)

Remote IP Address

(Command, Results

Storage Area)

Remote Port Number

(Command, Results

Storage Area)

7

 

 

0 Bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep-alive specification 0: Keep-alive disabled

1: Keep-alive enabled

The TCP socket number to be opened specified as 1 byte between 1 and 8.

The area in which the results of the command execution are stored. The first byte specifies the memory area and data type (variable type). The 2nd to 4th bytes specify the beginning address of the results storage area. Refer to page 158 for details about the variable types and addresses that can be spec- ified.

The TCP port number for communications with the socket is specified as 2 bytes (0 cannot be specified).

The following ports used for the Ethernet Unit's communications services can- not be specified.

TCP port No. used for FTP server (Default: 20, 21)

TCP port No. used for DNS server access (Default: 53)

TCP port No. used for SMTP server access (Default: 25)

TCP port No. used for POP server access (Default: 110)

TCP port No. used for HTTP server (Default: 80)

The maximum control time between receiving the open request and storing the result. If this set time limit is exceeded, the code for a timeout error will be set as the results storage response code. The value is set in units of 0.1 s. The timeout time is unlimited if the value is set to 0.

Specify the remote node’s IP address. If all zeroes are set, no remote node is specified and connection is awaited from any node. If any other value is set, connection is awaited from the specified remote node. The IP address of the connected remote node will be stored in the results storage area.

Specify the remote TCP port number with this command. If all zeroes are set, no remote TCP port number is specified. If any other value is set, it specifies the TCP port number of the remote node. The TCP port number of the con- nected remote node will be stored in the results storage area.

Precautions

Processing varies as shown in the table below according to the specified com- bination of remote IP address and remote TCP port number.

Remote IP address

Remote TCP port

Description

0

0

All connection requests received

0

Not 0

Received only when port number

 

 

matches.

Not 0

0

Received only when IP address

 

 

matches.

Not 0

Not 0

Received only when IP address and

 

 

port number matches.

173