Basic Settings

Section 2-9

Example: Using the CX-Programmer to Set the IP Address to 10.3.65.1

When an IP address is set in the Unit Setup, that value is displayed in the IP

Address Display/Setting Area in the DM Area words allocated for CPU Bus

Units.

When the IP address is set by the CX-Programmer, and the defaults are used for all other Unit settings, the settings will be as shown below.

Item

Status

 

 

IP address

Set by CX-Programmer.

 

 

Subnet mask

Uses value corresponding to IP address class.

 

 

Broadcast settings

4.3BSD specifications

 

 

Baud rate

Auto

 

 

TCP/IP keep-alive

120 minutes

 

 

IP router table

Not set. (IP routing not supported.)

 

 

Subnet Mask

For the subnet mask, all bits corresponding to the bits in the IP address used as either the net number or the subnet number are set to 1, and the bits corre- sponding to the host number are set to 0. These settings must be made when using an address conversion method other than the IP address table method.

If no subnet mask is set, or if an illegal value is set, the following values will be used depending on the IP address class.

Class

Subnet mask

 

 

Class A

255.0.0.0

 

 

Class B

255.255.0.0

 

 

Class C

255.255.255.0

 

 

With the default setting (0.0.0.0), a subnet mask corresponding to the IP address class is used.

Broadcast Settings

Set the method for specifying IP addresses when broadcasting.

Setting

Contents

 

 

All 1 (4.3BSD)

Broadcast with all ones for Host ID (4.3BSD specifications).

(Default)

 

 

 

All 0 (4.2BSD)

Broadcast with Host ID all zeros (4.2BSD specifications).