Honeywell 3.5 Installing the Control, Mounting the Control Cabinet, Installing the Cabinet Lock

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 11
Image 11
Installing the Control

S E C T I O N 3

Installing the Control

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.

Mounting the Control Cabinet

To mount the control cabinet, perform the following steps:

Step

1

2

UL

Action

Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.

DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED.

Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose.

To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2 Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require ATTACK RESISTANCE, use the cabinet included in the VISTA-ULKT kit.

Installing the Cabinet Lock

1.Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.

2.Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed.

3.When correctly positioned, push the lock until it is held securely by its snap tabs.

Use Part Number K4445 Lock (supplied).

CHECK

SNAP

POSITION

TAB

LOCKED

PUSH

 

 

ADEMCO

 

SNAP

UNLOCKED

TAB

CABINET DOOR

STEP 1

BOTTOM

PUSH

ON LOCK

UNTIL IT

IS SEATED

SECURELY

ADEMCO

 

STEP 2

_lock_snap-001-V0

 

cab

Figure 3-1: Installing the Lock

Grade A Mercantile Premises Listing Guidelines

The panel door must be supervised. Mount the clip-on tamper switch (supplied) to the cabinet’s right side wall as shown in the diagram below, and wire it to one of the hardwire zones.

Use a bell with a tamper-protected housing such as the AB12. The bell housing’s tamper switch and inner tamper linings must also be wired to the hardwire zone.

Assign the tampers’ hardwire zone to a burglary partition. Program the hardwire zone for day trouble/night alarm (zone type 5) when only one burglary partition is used. Program it for 24-hr. audible alarm (zone type 7) when more than one burglary partition is used.

All wiring between the bell and panel must be run in conduit. Remaining wires do not need to be run in conduit.

All wiring that is not run in conduit must exit from the knockout openings on the bottom or back of the cabinet.

All unused knockouts must be plugged using the disc plugs and carriage bolts (supplied), as indicated in the diagram below.

Fasten the cabinet door to the cabinet backbox using the 18 one-inch-long Phillips-head screws (supplied) after all wiring, programming, and checkout procedures have been completed.

3-1

Page 11
Image 11
Honeywell 3.5 manual Installing the Control, Mounting the Control Cabinet, Installing the Cabinet Lock, S E C T I O N, Step