Honeywell 3.5 Installing the Control, 3-15, Installing the 5800TM Module, Step Action, antennas

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 25
Image 25
Installing the 5800TM Module

Section 3 - Installing the Control

Installing the 5800TM Module

Installation of this module is necessary only if you are using a 5827BD or 5804BD Bi-directional device.

The address for the 5800TM must be enabled in the control’s Device Programming in the #93 Menu Mode as a keypad and then assigned to a partition.

To install the 5800TM, perform the following steps:

Step Action

1

Mount the unit using its accompanying

 

mounting bracket near the RF receiver.

 

The 5800TM must not be installed within

 

the control cabinet. It must be between

 

one and two feet from the receiver’s

 

antennas.

2

Set the module for the appropriate address.

 

For Address Setting 28 cut the red jumper;

 

for Address 29 cut the white jumper; for

 

Address 30 cut both jumpers.

5800 Series Transmitter Setup

5800 Series transmitters have the following characteristics:

Transmitters have built-in serial numbers that must be enrolled in the system using the #93 Menu Mode Programming, or input to the control via the downloader.

Transmitters do not have DIP switches (except 5827, described separately).

Some transmitters, such as the 5816 and 5817, can support more than one “zone” (referred to as loops or inputs). Each loop must be assigned a different zone number.

For button-type transmitters (wireless keys), such as the 5804 and 5804BD, you must assign a unique zone number to each individual button used on the transmitter.

Transmitter Input Types

All transmitters have one or more unique factory- assigned input (loop) codes. Transmitters can be programmed as one of the following types:

3

Connect the module’s wire harness to the

 

keypad terminals (6, 7, 8, and 9). Plug the

 

connector at the other end of the harness into

 

the module.

House ID Sniffer Mode

This mode applies only if you are using a wireless keypad (e.g., 5827) or bi-directional devices (e.g., 5804BD). Use the House ID Sniffer mode to make sure you do not choose a House ID that is in use in a nearby system. The House ID must be programmed for the receiver in Device Programming in the #93 Menu Mode.

To enter House ID Sniffer mode, enter your Installer

Type

RF (Supervised RF)

UR (Unsupervised RF)

BR (Unsupervised Button RF)

Description

Sends periodic check-in signals, as well as fault, restore, and low-battery signals. The transmitter must remain within the receiver’s range.

Sends all the signals that the RF type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises.

These send only fault signals. They do not send low-battery signals until they are activated. The transmitter may be carried off- premises.

Code + [#] + [2].

The receiver now “sniffs” out any House IDs in the area and displays them. Keep the receiver in this mode for about 2 hours. Use a House ID that is not displayed. Exit the Sniffer mode by entering your Installer Code

+ OFF.

As Sniffer mode effectively disables RF point reception, Sniffer mode cannot be entered while any partition is armed.

Transmitter Supervision

Supervised RF transmitters send a check-in signal to the receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised transmitter within a programmed period (field 1∗31), the “missing” transmitter number(s) and “CHECK” or “TRBL” are displayed. Unsupervised RF transmitters (5802MN, 5804) may be carried off the premises.

Some transmitters have built-in tamper protection, and annunciate a “CHECK” condition if covers are removed.

If a loss of supervision occurs on a transmitter programmed for Fire, it reports in Contact ID as a Fire Trouble (373), not Loss of Supervision (381), to the central station.

3-15

Page 25
Image 25
Honeywell 3.5 Installing the Control, 3-15, Installing the 5800TM Module, Step Action, antennas, Series Transmitter Setup