Table 3: Alarm Output Current Load

VISTA-40 Installation and Setup Guide

3.In Table 3, enter devices connected to the Alarm Output. Calculate alarm currents, then add to get the Alarm Output current subtotal.

Table 3: Alarm Output Current Load

 

 

 

 

 

Total Current

Device

 

Device Current X

Standby

 

Alarm

 

 

Model #

 

# of Units

 

 

 

 

 

 

 

 

 

 

 

4.In Table 4, enter the total calculated subtotals of all listed outputs from Tables 1 through 3, then add to get the combined current.

Table 4: Total VISTA-40 Current Load

Total Current

Standby Alarm

XXXXXX

XXXXXX

XXXXXX

XXXXXX

XXXXXX

XXXXXX

Polling Loop Subtotal (see Table 1)

Aux. Power Subtotal (see Table 2)

Alarm Output Subtotal (see Table 3)

VISTA-40 PCB Current (Includes 2- wire smoke detector loading on zone 1)

250mA

330mA

XXXXXX

Alarm Output Subtotal

(terminals 4 & 5 – 1.7A max.)

Total Current Load

Determining the Size of the Standby Battery

The cabinet supplied with the control panel can house batteries of up to 12V, 14AH (two 12V, 7AH batteries wired in parallel). The VISTA-ULKT kit provides a cabinet that can house batteries of up to 12V, 17.2AH and that may be used with this panel. The total standby current drawn from the auxiliary power and polling loop outputs combined must be limited to 270mA when 14AH batteries are used; and to 390mA

Use Table 5 to determine the required backup battery capacity and use Table 6 to determine the battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity.

5.Using the total calculated from Table 4, calculate the battery capacity required for the installation.

when 17.2AH batteries are used.

 

 

DO NOT use Gates batteries (sealed lead-acid

 

 

type). These batteries require a different

 

 

 

charging voltage than is supplied by the panel.

 

 

 

 

 

 

 

UL

 

Household Fire or Combination

 

Household/Fire/Burglary installations require

 

 

the use of a backup battery that is capable of

 

 

providing 24 hours of standby time followed by

 

 

4 minutes of alarm time. UL1023 Household

 

 

Burglary-only installations require the use of a

 

 

backup battery that is capable of providing 4

 

 

hours of standby time followed by 4 minutes of

 

 

alarm time.

Table 5: Battery Capacity Calculation Table

Capacity

Formula

 

 

 

Standby

For 4-hour standby time:

Capacity

Total standby current X 4 hours

 

X 1.4 contingency factor.

 

For 24-hour standby time:

 

Total standby current X 24

 

hours X 1.1 contingency factor.

Alarm

For 4-, 5-, or 15-minute alarm

Capacity

time:

 

 

Total alarm curr.

 

 

X

0.067 (4 min)

 

X

0.250 (15 min)

Calculated

Value

 

Total
Add standby and alarm

 

 

 

Capacity

capacities

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-26

Page 36
Image 36
Honeywell ZyAIR G-3000 Determining the Size of the Standby Battery, VISTA-40Installation and Setup Guide, 3-26, Device