Honeywell ZyAIR G-3000, 3.5 manual VISTA-40Installation and Setup Guide, Terminals, On Control

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 16
Image 16
TERMINALS

VISTA-40 Installation and Setup Guide

Handset

{

26

27

TERMINALS

 

ON CONTROL

 

BROWN (TIP)

GREY (RING)

{GROUND

Incoming

 

Telco Line

 

28

29

30

GREEN(TIP)

(RING)RED

DIRECT

 

 

CONNECT

 

 

CORD

 

 

PLUG

EARTH GROUND

 

INCOMING TELCO LINE

TIP

RING

RJ31X

TIP

 

PREMISES

RING

 

JACK

 

PHONES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3-8: Telephone Line Connections

Wiring Burglary, Panic and Smoke Detector Devices to Zones 1-9

The maximum zone resistance is 100 ohms for zones 1 and 8, and 300 ohms for all other zones (excluding the 2K EOL resistor).

To wire burglary and panic devices to zones 1-9, connect sensors/contacts to the hardwire zone terminals (10 through 23). See Figure 3-9. Connect N.C. and N.O. devices as follows:

Connect N.C. devices in series with the high (+) side of the loop. The 2K EOL resistor must be connected in series with the devices, following the last device.

Connect N.O. devices in parallel (across) the loop. The 2K EOL resistor must be connected across the loop wires at the last device.

Red Jumper

ZONE 2 ZONE 3

ZONE 4 ZONE 5

ZONE 6 ZONE 7

ZONE 8 ZONE 9

10

11

12

13

14

15

16

17

18

19

20

21

 

22

23

ZONE 1

 

 

 

 

 

 

 

 

 

LATCHING TYPE GLASS

 

Programmable Response

 

 

supportsNO/NC Burg contacts)

+

-

+

 

 

 

+

-

+

BREAK DETECTORS

(Fast/Normal) Loop

2-WIRE SMOKE DETECTOR LOOP

N.C.

 

N.C.

 

 

 

N.C.

 

N.C.

N.O.

 

N.O.

 

 

 

N.O.

 

N.O.

2k EOLR

 

2k EOLR

 

2k EOLR

 

2k EOLR

 

(Also

 

 

 

+

-

+

 

 

 

+

 

-

+

 

 

 

 

 

 

 

 

 

 

 

+

-

Fire

 

 

 

 

 

GLASS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Usage

 

 

 

 

 

 

 

BREAK

 

 

 

SMOKE

 

 

 

N.C.

 

N.C.

 

 

 

 

 

 

N.C.

 

 

 

 

 

 

 

 

 

N.C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N.C.

 

 

 

 

N.O.

 

N.O.

 

 

 

N.O.

 

 

N.C.

 

 

Burg.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Usage

2k EOLR

 

2k EOLR

 

 

 

 

 

 

 

N.O.

 

 

 

 

 

2k EOLR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hw_zones-001-V0

 

Zone resistance (Excluding EOLR):

2k EOLR

ZONE 1,8: 100 OHMS MAXIMUM

ALL OTHER ZONES: 300 OHMS MAXIMUM

 

Zone response time:

ZONES 1-8: 350mSec-500mSec

ZONE 9: Programmable for Fast: 10mSec-15mSec Normal: 350mSec-500mSec

(default response)

Figure 3-9: Wiring Connections for Zones 1-9

3-6