Honeywell 3.5 Telephone Line Connections, Installing the Control, Supervising the Alarm Output

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 15
Image 15
Supervising the Alarm Output

Section 3 - Installing the Control

POLARIZING DIODES

(MUST MOUNT AT INDICATING DEVICE)

PANEL BELL

BELL

BELL

PANEL BELL

TO

HORNOTHER DEVICES

NONPOLARIZED BURGLARY

POLARIZED FIRE

 

INDICATING DEVICES

INDICATING DEVICE

non_polar_devices

Figure 3-7: Wiring Nonpolarized Burglary Devices

Supervising the Alarm Output

Using a Siren Driver

 

To wire the alarm output using the supervision feature, perform the following steps:

Step Action

1Wire polarized fire-indicating devices to the alarm output as shown in Figure 3-6.

2Wire nonpolarized burglary indicating devices to the alarm output using a polarizing diode (two 2A diodes supplied), as shown in Figure 3-7.

3Program Zone 70 with a response type of 05 (trouble by day/alarm by night).

The minimum load on the alarm output must exceed 5mA at 12V for proper supervision operation.

To install a siren driver, perform the following steps:

Step Action

1Mount the siren driver in the panel’s cabinet.

2Wire the siren driver to the control and to the speaker(s). (See the driver’s instructions.)

3Cut the blue jumper on the upper left-hand corner of the panel’s PC board.

4Program Zone 70 with no response type (00).

UL

If a device such as a siren driver with a high-

resistance trigger input (drawing less than 5mA)

 

is used in a UL Household Fire installation, the

 

siren driver must independently supervise siren

 

speaker wiring.

 

 

Disabling the Supervision of the Alarm Output

To install the alarm output and disable the supervision feature, perform the following steps:

Step

1

2

Action

Wire the devices to terminals 4 and 5, observing polarity if necessary.

Cut the blue jumper on the upper left-hand corner of the panel’s PC board.

3

Program Zone 70 with no response type (00).

Telephone Line Connections

Connect the main dialer output to telephone company lines using the RJ31X cables supplied.

UL

The telephone line inputs have overvoltage

protection in accordance with UL1459, as

 

specified in UL985/UL1023.

 

 

To prevent the risk of shock, disconnect phone lines at the telco jack before servicing.

If the communicator is connected to a PABX, be sure it has a backup power supply that can support the PABX for 24 hours (central station) or 60 hours (remote station). Many PABXs are not power-backed up, and this can result in a communication failure if power is lost.

Reporting Formats

The system supports the following formats: ADEMCO Low Speed 3+1; 4+1; 4+2; Sescoa/Radionics 3+1; 4+1; 4+2; ADEMCO 4+2 Express; ADEMCO High Speed; ADEMCO Contact ID

3-5

Page 15
Image 15
Honeywell 3.5 Telephone Line Connections, Installing the Control, Supervising the Alarm Output, Using a Siren Driver, Step