Transmitter Battery Life

VISTA-40 Installation and Setup Guide

Transmitter Battery Life

Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation.

The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system.

Some transmitters (e.g., 5802, 5802CP, and 5803) contain long-life but nonreplaceable batteries. At the end of their life, the complete unit must be replaced (and a new serial number enrolled at the control).

Button-type transmitters (e.g., 5801, 5802, 5802CP and 5803) should be periodically tested, as these transmitters do not send supervisory check-in signals.

To test the transmitters using the Transmitter ID Sniffer mode and the Go/NoGo Test Mode, see SECTION 10: Testing the System for the procedures.

Compatible 5800 Series Transmitters

Model

5801

5802

5802CP

5802MN

5802MN2

5804

5804BD

5804BDV

Product

Panic Transmitter

Pendant (Personal Emergency Transmitter)

Belt Clip (Personal Emergency Transmitter)

Miniature (Personal Emergency Transmitter)

Miniature (Personal Emergency Transmitter)

Wireless Key Transmitter

Wireless Key Bi-directional Transmitter

Wireless Key Bi-directional Transmitter with Voice

Input Type

UR or RF

BR Only

UR or RF

UR or RF

BR Only

BR Only

BR Only

Model

5806/5807/

5808

5816

5816MN

5816TEMP

5817

5818

5827

5827BD

5849

5850

5890

5890PI

Product

Wireless Photoelectric Smoke Detectors

Door/Window Transmitter

Miniature Door/Window Transmitter

Temperature Sensor Transmitter

Multi-Point Universal Transmitter

Recessed Transmitter

Wireless Keypad

Wireless Bi-directional Keypad

Glassbreak Detector

Glassbreak Detector

PIR Detector

PIR Detector with Pet Immunity

Input Type

RF

RF

RF

RF

House ID

House ID

RF

RF

RF

RF

Installing Relay Devices

The VISTA-40 support up to 8 relays. Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). The 4204 and/or X-10 devices may be used as relay devices.

Installing the 4204 Relay Modules

Each 4204 module provides 4 relays with Form C (normally open and normally closed) contacts.

The relay module will not operate until the device address you have set the DIP switches for is enabled in the control’s Device Programming in the #93 Menu Mode.

To install the relay modules, see Figures 3-21and 3-22 and perform the following steps:

Step Action

1Set the 4204 or 4204CF’s DIP switches for a device address 01-15.

Do not use an address being used by another device (keypads, RF receivers, etc.).

2Mount the 4204 and 4204CF Modules per the instructions provided with them.

3Connect the module’s wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of harness) to the module.

If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire run lengths. Refer to the instructions provided with the 4204CF for its maximum permissible wire lengths.

Wire Gauge

Maximum Length

#22

125 feet

#20

200 feet

#18

300 feet

#16

500 feet

 

 