Installing External Sounders

VISTA-40 Installation and Setup Guide

Installing External Sounders

The VISTA-40 provides a bell circuit output for operating fire and burglary alarm notification appliances. The alarm output is rated as follows: 10VDC – 14VDC, 1.7A max., power-limited.

The output has the following options:

Selectable for supervision.

Selectable for confirmation of arming ding.

Selectable to chime when entry/exit or perimeter zones are faulted.

Selectable for no timeout or timeout of 2-30 minutes.

UL

Burglary bell circuits must be programmed

for a timeout of 16 minutes or longer.

 

For Household Fire and combination

 

Household Fire/Burglary installations, the

 

total current drawn from the auxiliary power,

 

polling loop, and alarm output combined

 

must not exceed 750mA.

 

For Household Burglary installations, the

 

total current drawn from the alarm output

 

must not exceed 1.7A. A battery must be

 

installed, as it supplies the current for the

 

combined auxiliary power, polling loop, and

 

alarm output in excess of 750mA.

Alarm Output Supervision

When supervision is enabled, the VISTA-40 monitors the alarm output wiring for open and short circuit faults while the output is inactive. The system provides a trouble indication (Zone 70) when an open occurs; or when a short occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth ground.

The VISTA-40 indicates the trouble condition regardless of whether the system is armed or disarmed. The zone displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1. The Contact ID event code is 321, Bell Trouble. The trouble is cleared from the display by entering the user code + OFF.

Wiring the Alarm Output

The wiring of the alarm output depends upon whether you are going to supervise the output or not. Use the appropriate procedure below for your application.

UL

Use only UL Listed sounding devices for UL

installations.

Compatible Alarm Indicating Devices

UL1023 Household Burglary Installations

For Household Burglary installations, the total current drawn from the alarm output must not exceed 1.7A. A battery must be installed, as the battery supplies current from the combined auxiliary power, polling loop, and alarm output in excess of 750mA.

UL985 Household Fire or Combination Household Fire/Burglary Installations

For installations that must provide UL Listed protection, the total combined current drawn from the alarm output, auxiliary power output, and polling loop must not exceed 750mA in order to comply with the

Model Number

719

747

AB12

System Sensor MA 12/24D

System Sensor P12575

Wheelock

AS-121575W

Device Type

Compact Outdoor Siren

(not UL Listed)

Indoor Siren

Grade A Bell

Fire Piezo Horn

Fire Horn/Strobe

Fire Horn/Strobe

Polarizing Diode

Yes

Yes

Yes

No

No

No

battery independence requirements. If, for example, two System Sensor PA400 piezo alarm sounders, wired in parallel, are used (24mA total), then 726mA (750mA

24mA) is available for auxiliary output and polling loop use.

Non-UL Installations

For non-UL installations, the total current drawn from this output can be up to 1.7 amps. A battery must be installed, as the battery supplies current in excess of 750mA. Up to two 719 sirens can be used wired in parallel.

UL

This control complies with National Fire

Protection Association (NFPA) requirements for

 

temporal pulse sounding of fire notification

 

appliances.

 

 

1 2 3 +

4 5

-

6 7 8

ALARM SOUNDER OUTPUT: 1-VDC - 13.8VDC

1.7A MAXIMUM

+-

BELL

V0-001

HORN-devices

_fire

Figure 3-6: Wiring Polarized Fire Devices

3-4

Page 14