Honeywell ZyAIR G-3000, 3.5 manual Installing the Audio Alarm Verification Module, 3-22

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 32
Image 32
Installing the Audio Alarm Verification Module

VISTA-40 Installation and Setup Guide

Installing the Audio Alarm Verification Module

UL

Audio Alarm Verification (AAV) is not permitted

in UL installations.

685 Receiver software must be rev. 4.6 or higher. Earlier versions will not hold the phone line connection.

Contact ID code for “Listen-in to Follow” is 606. Contact ID is the only reporting format that will send a “Listen-in to Follow.”

If you are also using a 4285/4286 VIP Module, be sure to follow Figure 3-30when making connections.

The UVS consists of a UVCM and at least one UVST. The UVCM board has a DC power jack and a 34- position terminal block for making connections to a DC power source, UVSTs, telephone lines, music source, or to the 4286 VIP Module; and to a control panel’s voice trigger and bell outputs (if required). Refer Figure 3-28for wiring connections. For a detailed explanation of the wiring connections and the functions of the DC power jack and terminal block positions, refer to the installation instructions that accompany the UVS.

If the phone plug is disconnected from the control, the premise’s phones will not operate.

NOTES:

When the AAV indicates that the audio alarm verification session is completed, all keypad sounds are restored. Sirens are restored if the alarm timeout period has not expired.

As part of its fail-safe software, the control limits all audio alarm verification sessions to 15 minutes. This is because once the session begins, the AAV Module controls the duration.

If a new Fire alarm should occur during a session, the control breaks the phone connection and sends the new Fire Alarm report, then re-triggers the AAV Mode. All other dialer messages triggered during ongoing conversation are held until either the AAV Module signals that it is inactive, or the 15-minute timeout occurs.

3-22

Page 32
Image 32
Honeywell ZyAIR G-3000, 3.5 Installing the Audio Alarm Verification Module, VISTA-40Installation and Setup Guide, 3-22