Honeywell 3.5 manual Installing the Control, 3-11, Step Action, 16 Polling Loop Connections to the

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 21
Image 21
Figure 3-16: Polling Loop Connections to the

Model Number Type

7500

 

Single Technology Glassbreak Detector

 

9500

 

Dual Technology Glassbreak Detector

 

4209U

 

Universal Group Zoning Module

 

4193SN

 

Serialized 2-Zone Expander

 

4293SN

 

Serialized 1-Zone Expander

 

4190SN

 

Serialized 2-Zone Expander

 

998MX

 

Serialized PIR

 

 

 

 

UL

The 4208 must be mounted either inside the

 

control panel’s cabinet or in a separate

 

enclosure that has a tamper-supervised cover.

The 4190WH right loop must not be used, and the left loop must be EOLR-supervised.

The 4278 right loop cannot be used.

The 4194 is not UL Listed.

The 4297 must be powered from the control panel’s Auxiliary Power Output or from a UL Listed supplementary power supply.

The 7500 and 9500 detectors are not UL Listed.

For new polling loop installations, always use twisted pair wiring. In many cases, existing non-twisted pair wiring may be used, but it is more susceptible to interference from other sources, and may be problematic in installations with long wire runs or in high noise environments.

Always locate polling loop wiring at least six inches (15cm) of AC power, telephone, or intercom wiring. The polling loop carries data between the control panel and the devices; interference on this loop can cause an interruption of communication. The polling loop can also cause outgoing interference on the intercom or phone lines. If this spacing cannot be achieved, shielded wire must be used. (Note that the maximum total wire length supported is cut in half when shielded wire is used.)

Section 3 - Installing the Control

To install polling loop devices, perform the following steps:

Step Action

1Select devices from the list of compatible devices shown previously.

2Set the DIP switches in the device (if required). Refer to the device’s instructions for the DIP Switch Tables.

3Mount each device in the desired location. Refer to the device’s instructions.

4Run wires from the control panel to each device on the polling loop (see Figure 3-16). No individual wire run may exceed the lengths shown in the following table.

Maximum Polling Loop Wire Runs

 

Wire Gauge

Max. Length

 

 

#22 gauge

650 feet

 

 

#20 gauge

950 feet

 

 

#18 gauge

1500 feet

 

 

#16 gauge

2400 feet

 

 

 

 

 

5Wire each device to the polling loop, making sure of the correct polarity (refer to the device’s instructions).

NOTE: If you are using serial number devices, and intend to enroll each device through the keypad automatically, wire no more than 25 of these devices to the control at a time. Then power up and program them before connecting the next 25. Leave previously enrolled devices connected. If you intend to manually enter the serial numbers through the keypad or through Compass downloading software, all the devices may be connected before powering up to program.

21

22

23

24

25

No more than 64mA may be drawn on any individual wire run.

When a star configuration is used, the total length of all wire runs combined cannot exceed 4000 ft (2000 ft. if you are using unshielded wire in conduit or shielded wire).

IMPORTANT NOTE: If the installation exceeds or deviates from these parameters, refer to the application note on the Honeywell website for additional information. To access the application note:

1.

Go to the honeywell.com/security website

2.

Click the Honeywell Security & Custom Electronics link.

POLLING LOOP RATING: 128mA MAXIMUM

+ LOOPPOLLING

4190 RPM

4192SD

SMOKE

4278

PIR

-

TO RIGHT LOOP

poll_loop-001-V0

3.

Click the Commercial link.

4.

Click the Documentation link.

5.

Click the V-Plex Application Note.

Figure 3-16: Polling Loop Connections to the

VISTA-40

3-11

Page 21
Image 21
Honeywell 3.5, ZyAIR G-3000 manual Installing the Control, 3-11, Step Action, 16 Polling Loop Connections to the, VISTA-40