Panel Earth Ground Connections

 

Section 3 - Installing the Control

Panel Earth Ground Connections

 

In order for the lightning transient protective devices in

AC Power Outlet Ground: Available from 3-

this product to be effective, the designated earth ground

prong, 120VAC, power outlets only. To test the

terminal (terminal 30) must be terminated in a good

integrity of the ground terminal, use a three-wire

earth ground. Recommended wire gauge for the ground

circuit tester with neon lamp indicators, such as

connection is #16 AWG, run no farther than 30 feet.

the UL-Listed Ideal Model 61-035, or equivalent,

The following are examples of good earth grounds

available at most electrical supply stores.

available at most installations:

 

Metal Cold Water Pipe: Use a noncorrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured.

The panel requires the earth ground connection for its lightning transient protection devices.

Determining the Control’s Power Supply Load

Use the tables that follow to calculate the total current for the Auxiliary Power, the Alarm Output, and the Polling Loop. In each table, multiply each device’s standby and/or alarm current by the number of units used.

1.In Table 1, enter devices used on the polling loop. Calculate total current draw on the polling loop.

Table 1: Total Polling Loop Current Draw

Polling Loop Device Current # of Units Total

2.In Table 2, enter devices used on Auxiliary Power. Calculate standby and alarm currents, then add to get Auxiliary Power current subtotal.

Table 2: Auxiliary Power Current Load

 

 

 

 

 

Total Current
Device

 

Device Current X

 

Standby

 

Alarm

 

 

 

Model #

 

# of Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Polling Loop Subtotal

(terminals 24 & 25 – 64mA)

Auxiliary Power Subtotal

(terminals 6 & 7 – 750mA max.)

The total current cannot exceed 64mA. If total load exceeds 64mA, then a 4297 Loop Extender Module can be used. Note that the total number of points connected to the panel cannot exceed 55.

3-25

Page 35
Image 35