Honeywell 3.5 manual Regulatory Agency Statements, A P P E N D I X A, UL Installation Requirements

Models: ZyAIR G-3000 3.5

1 96
Download 96 pages 54.8 Kb
Page 73
Image 73
A P P E N D I X A

A P P E N D I X A

Regulatory Agency Statements

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

UL Installation Requirements

The following requirements apply to both UL Residential and UL Commercial Burglary installations:

All partitions must be owned and managed by the same person(s).

All partitions must be part of one building at one street address.

The audible alarm device(s) must be placed where it/they can be heard by all partitions.

The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the cabinet door (not supplied with VISTA-40) or by installing a UL Listed passive infrared detector positioned to detect cabinet access. Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be used for multiple-partitioned systems.

Remote downloading and auto-disarming are not UL Listed features.

NOTE: UL Commercial Burglary installations require the attack resistant cabinet. The cabinet is included in the VISTA-ULKT kit.

UL609 Grade A Local Mercantile Premises/Local Mercantile Safe & Vault

Use the following guidelines for a Grade A Local Mercantile Premises/Local Mercantile Safe & Vault installation:

All zones must be configured for EOLR supervision (41=0). Wireless sensors may not be used. If 4190WH RPMs are used, set field 24 to “0” to enable tamper detection.

Attach a door tamper switch (supplied) to the VISTA-40 cabinet backbox. For safe and vault installations, a shock sensor (not supplied) must also be attached to the backbox. (Also see SECTION 3: Installing the Control)

Wire an AB12 Grade A Bell/Box to the bell output. Bell wires must be run in conduit. Program the bell output for a timeout of 16 minutes or longer timeout and for confirmation of arming ding. (Also see SECTION 3: Installing the Control.)

Wire the VISTA-40 tamper switch and AB12 Bell/Box tamper switches to any EOLR-supervised zone (zones 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be used for multiple-partitioned systems.

Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds.

UL365 Police Station Connected Burglar Alarm

Follow the instructions for UL609 local installations given above.

For Grade A Service:

You may use the VISTA-40 dialer alone, or the 7720 Long Range Radio alone.

When using the dialer, program it to send Burglary Alarm, Low Battery, and Communicator Test reports. Field 27 must be set to “024” (or less).

If you are using the 7720, connect it to the VISTA-40 burglary/audible panic alarm trigger.

For Grade AA Service:

You must use a 7920SE Long Range Radio.

Connect the 7920SE to the VISTA-40 burglary/audible panic alarm trigger.

A-1

Page 73
Image 73
Honeywell 3.5 manual Regulatory Agency Statements, A P P E N D I X A, UL Installation Requirements, For Grade A Service