SSI America user manual Model 9200 Programmable Dual-loop Controller

Page 59

Model 9200 Programmable Dual-loop Controller

DEV_AL This deviation alarm “opcode” is used to turn the temperature or atmosphere deviation alarms ON or OFF.

The option values are:

OFF, turns off both the temperature and atmosphere alarms;

TEMPERATURE, turns on the temperature alarm and turns off the atmosphere alarm;

ATMOSPHERE, turns on the atmosphere alarm and turns off the temperature alarm; and

BOTH, turns on both the temperature and the atmosphere alarms.

The band limit can be changed by the SET_WAIT “opcode”.

DOW_INQ This “opcode” checks the real time clock for the day of the week. This is useful for performing operations on a weekly basis on a specific day. The option data is the day of the week, i.e. SUN, MON, TUE, WED, THU, FRI, and SAT.

EVT_IN This “opcode” waits for an input event to be turned ON or OFF depending on the option value. The option value is the event number followed by either ON or OFF.

If temperature data and or atmosphere data are specified, they are considered setpoints and will be sent to the appropriate controller.

EVT_OUT The Event Output “opcode” turns ON or OFF an output event based upon the option value. . The option value is the event number followed by either ON or OFF.

If temperature data and or atmosphere data are specified, they are considered setpoints and will be sent to the appropriate controller.

G_Ramp This is a guaranteed ramp “opcode”. The temperature and or atmosphere process value must be within the deviation band to allow the ramp timer to run. The option values are the ramp time in hours and minutes, Temperature and / or Atmosphere Setpoint. The band limit can be changed by the SET_WAIT “opcode”.

G_SOAK This is a guaranteed soak “opcode”. The temperature process value must be within the deviation band to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT “opcode”.

G_SOAK High This is a guaranteed soak high “opcode”. The temperature process value must be above the deviation band to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT “opcode”.

G_SOAK Low This is a guaranteed soak low “opcode”. The temperature process value must be below the deviation band to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT “opcode”.

GOSUB The goto subroutine “opcode” is used to call a program and then return to the calling program. This is used to execute standard routines that can be used by many programs. GOSUBs can be stacked up to eight levels. The option data is the program number.

HIGH_AL This “opcode” is used to enable a high limit alarm on the temperature process and/or the atmosphere process. The temperature data is the high limit point for the temperature process. The atmosphere data is the high limit point for the atmosphere process. This alarm remains active until the program ends.

HIGH_PO This “opcode” is used to enable a high limit alarm on the temperature percent output and/or the atmosphere percent output. The temperature data is the high limit point for the temperature

SSi Manual SERIES 9200

59

Programmable Dual-loop

Image 59
Contents Model 9200 Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller 24VDC / 1 AMP Ohms Total IP10 hand protected Model 9200 Terminals Connections Model 9200 Programmable Dual-loop Controller SSi requirement Installation Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Configuration Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Adam VC Base Aipc Model 9200 Programmable Dual-loop Controller Step Opcode Temperature Atmosphere Option Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Calibrate Span input 1 range Span input 2 range Zero input 3 range Zero Output Span Output Enter measured output current mA Supervisor Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Programs Parameter Value Series 9200 Opcodes Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Applications Information Series 9200 Factory defaults August 17 Rev August 6 Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller OPT Code Temp SET PT Rev Description Date