Status of | Indication | Malfunction | Content of diagnosis | Inspection location/method |
| Remedy | ||
indoor/ | by LED1 | No. dis- |
|
|
|
|
| |
outdoor | on out- | played on |
|
|
|
|
| |
units | door unit | main unit |
|
|
|
|
| |
| *2 | display sec- |
|
|
|
|
| |
|
| tion *1 |
|
|
|
|
| |
|
| Main | Sub- | Main category |
|
|
| |
|
| cate- | cate- |
|
|
|
|
|
|
| gory | gory |
|
|
|
|
|
Indoor/ |
| 19 | Indoor unit fan | Indoor unit fan error | (1) Check the indoor fan | (1) Replace the indoor fan | ||
outdoor |
|
|
|
|
| motor for proper rotating |
| motor. |
units in |
|
|
|
|
| operation.(Check fan |
|
|
complete |
|
|
|
|
| lock.) |
|
|
shutdown |
|
|
|
|
| (2) Check the lead wire of the | (2) Replace the indoor fan | |
|
|
|
|
|
| indoor fan motor for open- |
| motor. |
|
|
|
|
|
| circuit. |
|
|
|
|
|
|
|
| (3) Check CN1 of the indoor | (3) | Correct the installa- |
|
|
|
|
|
| unit fan motor for secure |
| tion of CN1 of the |
|
|
|
|
|
| installation. |
| indoor fan motor. |
|
|
|
|
|
| (4) No abnormality found in | (4) | Replace the indoor |
|
|
|
|
|
| above inspections (1) |
| unit control PWB. |
|
|
|
|
|
| through (3). |
|
|
Indoor/ |
| 20 | Indoor unit con- | EEPROM data error | (EEPROM read data |
| Replace the indoor | |
outdoor |
|
|
| trol PCB |
| error) |
| unit control PWB. |
units in |
|
|
|
|
|
|
|
|
operation |
|
|
|
|
|
|
|
|
Indoor/ |
| 88 |
| Control and dis- | Communication | (1) Check for disconnected | (1) | Insert connectors cor- |
outdoor |
|
|
| play PCB | error | connector between control |
| rectly, or replace con- |
units in |
|
|
|
|
| PCB and display PCB, |
| trol PWB. |
operation |
|
|
|
|
| and |
|
|
|
|
|
|
|
| wires. |
|
|
|
|
|
|
|
| (2) Check that control PCB | (2) | Replace control PWB. |
|
|
|
|
|
| outputs signals correctly. |
|
|