Sharp AE-X9FR, AY-XP12FR, AY-XP7FR, AY-XP9FR, AE-X7FR, AE-X12FR service manual Main

Page 10

 

 

 

 

 

 

 

 

 

AYXP7FR

 

 

 

 

 

 

 

 

 

Status of

Indication

Malfunction

Content of diagnosis

Inspection location/method

 

Remedy

indoor/

by LED1

No. dis-

 

 

 

 

 

 

outdoor

on out-

played on

 

 

 

 

 

 

units

door unit

main unit

 

 

 

 

 

 

 

*2

display sec-

 

 

 

 

 

 

 

 

tion *1

 

 

 

 

 

 

 

 

Main

Sub-

Main category

Sub-category

 

 

 

 

 

 

cate-

cate-

 

 

 

 

 

 

 

 

gory

gory

 

 

 

 

 

 

Indoor/

11

11

-0

Outdoor unit DC

Outdoor unit DC fan

(1)

Check connector CN3 of

(1)

Correct the installa-

outdoor

times

 

 

fan

rotation error

 

the outdoor unit DC fan

 

tion.

units in

 

 

 

 

 

 

motor for secure installa-

 

 

complete

 

 

 

 

 

 

tion.

 

 

shutdown

 

 

 

 

 

(2)

Check the outdoor unit fan

(2)

Replace the outdoor

 

 

 

 

 

 

 

motor for proper rotation.

 

unit fan motor.

 

 

 

 

 

 

(3)

Check fuse FU3.

(3)

Replace the outdoor

 

 

 

 

 

 

 

 

 

unit control PWB

 

 

 

 

 

 

 

 

 

assembly.

 

 

 

 

 

 

(4)

Outdoor unit control PWB

(4)

Replace the outdoor

 

 

 

 

 

 

 

 

 

unit control PWB

 

 

 

 

 

 

 

 

 

assembly.

Indoor/

13

13

-0

DC compressor

Compressor startup

(1)

Check the colors (red,

(1)

Correct the installa-

outdoor

times

 

 

 

error

 

white, orange) of the com-

 

tion.

units in

 

 

 

 

 

 

pressor cords for proper

 

(U: Red, V: White, W:

complete

 

 

 

 

 

 

connection. (PWB side,

 

Orange)

shutdown

 

 

 

 

 

 

compressor side)

 

 

 

 

 

-1

 

Compressor rota-

(2)

Check if the IPM terminal

(2)

Replace the outdoor

 

 

 

 

 

tion error

 

resistance values are uni-

 

unit control PWB

 

 

 

 

 

(120° energizing

 

form.

 

assembly.

 

 

 

 

 

error)

(3)

No abnormality found in

(3)

Replace the outdoor

 

 

 

 

 

 

 

above inspections (1) and

 

unit control PWB

 

 

 

 

 

 

 

(2).

 

assembly.

 

 

 

 

 

 

(4)

No abnormality found in

(4)

Replace the compres-

 

 

 

 

 

 

 

above inspections (1)

 

sor.

 

 

 

 

 

 

 

through (3).

 

 

Indoor/

14

14

-0

Outdoor unit

PAM over voltage

(1)

Check the AC power sup-

(1)

Connect stable power

outdoor

times

 

 

PAM

error

 

ply voltage for fluctuation.

 

supply.

units in

 

 

 

 

Compressor rota-

(2)

No abnormality found in

(2)

Replace the outdoor

complete

 

 

 

 

tion error

 

above inspection (1).

 

unit control PWB

shutdown

 

 

 

 

 

 

 

 

assembly.

Indoor/

 

 

-1

 

PAM clock error

(1)

Check the PAM clock for

(1)

Replace the outdoor

outdoor

 

 

 

 

 

 

proper input.

 

unit control PWB

units in

 

 

 

 

 

 

 

 

assembly.

operation

 

 

 

 

 

 

 

 

 

Indoor

 

17

-0

Wires between

Serial open-circuit

(1)

Check the wires between

(1)

Connect stable power

unit in

 

 

 

units

 

 

units.

 

supply.

operation

 

 

 

 

 

(2)

Check voltage between

(2)

Replace the outdoor

Outdoor

 

 

 

 

 

 

Nos. 1 and 2 on the

 

unit control PCB

unit in

 

 

 

 

 

 

indoor/outdoor unit termi-

 

assembly.

complete

 

 

 

 

 

 

nal boards.

 

 

shutdown

 

 

 

 

Outdoor unit does

(1)

Check the wires between

(1)

Correct the wiring.

 

 

 

 

 

not turn on due to

 

units.

 

 

 

 

 

 

 

erroneous wiring

(2)

Check the outdoor unit

(2)

Replace the fuse/out-

 

 

 

 

 

 

 

fuse.

 

door unit control PCB

 

 

 

 

 

 

 

 

 

assembly.

 

 

 

 

 

 

(3)

Check 15-V, 13-V and 5-V

(3)

Replace the outdoor

 

 

 

 

 

 

 

voltages on the PWB.

 

unit control PCB

 

 

 

 

 

 

 

Check resistance between

 

assembly.

 

 

 

 

 

 

 

IPM terminals.

 

 

 

 

 

 

 

 

(4)

Check pins No. 5 and 7 of

(4)

Replace the outdoor

 

 

 

 

 

 

 

connector CN3 of the out-

 

unit fan motor.

 

 

 

 

 

 

 

door unit fan motor for

 

 

 

 

 

 

 

 

 

short-circuit.

 

 

 

 

 

 

 

 

(5)

Outdoor unit control PCB

(5)

Replace the outdoor

 

 

 

 

 

 

 

 

 

unit control PCB

 

 

 

 

 

 

 

 

 

board.

 

 

18

-0

 

Serial short-circuit

(1)

Check the wires between

(1)

Correct the wiring.

 

 

 

 

 

 

 

units.

 

 

 

 

 

-1

 

Serial erroneous wir-

(1)

Check the wires between

(1)

Correct the wiring.

 

 

 

 

 

ing

 

units.

 

 

3 – 16

Image 10
Contents Models AY-XP7FR AE-X7FR AY-XP9FR AE-X9FR AY-XP12FR Specification AY-XP7FR AE-X7FRAY-XP9FR AE-X9FR Model Indoor Unit Outdoor Unit Items AY-XP9FR AE-X9FRAY-XP12FR AE-X12FR Indoor unit External DimensionOutdoor unit Wiring Diagrm Indooa unit Outdooa unitTroubleshooting Guide Self-Diagnosis Function and Display ModeStatus AYXP7FR Main AYXP7FR Inter-unit wiring error mode Symptom AY-XP7FR Performance CurvesAY-XP9FR AY-XP12FR