Sharp AY-XP7FR, AY-XP12FR, AE-X7FR Troubleshooting Guide, Self-Diagnosis Function and Display Mode

Page 7

AYXP7FR

[8] TROUBLESHOOTING GUIDE

1. Self-Diagnosis Function and Display Mode

To call out the content of the self-diagnosis memory, hold down the emergency operation button for more than 5 seconds when the indoor unit is not operating.

The number of indications displayed by the LEDs on the outdoor unit differs from that for the 2001 cooling unit models (for detailed display of mal- function information).

The display of malfunction No. differs from that of the 2001 cooling unit models. To show detailed malfunction information, two types of numbers flash alternately. (example: "21" ←→ "-0")

1)The content of the self-diagnosis memory can be called out and displayed on the seven-segment display section on the indoor unit. (The error data cannot be called out for display by the LED on the outdoor unit.)

2)If the power cord is unplugged from the AC outlet or the circuit breaker is turned off, the self-diagnosis memory loses the stored data.

a)The self-diagnosis display function of the indoor unit indicates the content of diagnosis by showing the error main category (number) and the error sub-category (-number) alternately in 1-second intervals on the seven-segment display section of the indoor unit.

Example of self-diagnosis display on indoor unit: Compressor high-temperature error

'TTQTOCKPECVGIQT[ 'TTQTUWDECVGIQT[

b)The self-diagnosis display function of the outdoor unit indicates the error information by flashing LED1 on the outdoor unit according to the con- tent of self-diagnosis.

The self-diagnosis display function of the outdoor unit is active only for about 3 to 10 minutes after self-diagnosis is performed during operation, and the display returns to normal condition after this display period.

The content of self-diagnosis cannot be called out by the self-diagnosis display function of the outdoor unit. Example of self-diagnosis display on outdoor unit: Compressor high-temperature error

ON OFF

1 sec 1 sec 0.6 sec 1 sec 0.6 sec 1 sec 1 sec

1 sec 0.6 sec 1 sec 0.6 sec 1 sec 1 sec

c) The content of diagnosis is transferred to the indoor unit via serial communication, but it does not trigger a complete shutdown operation.

: Flashes in 2-sec intervals (normal), : On, : Off, : Flashes 3 times in 0.2-sec intervals (When LED1 on the outdoor unit flashes in 2-sec intervals, the outdoor unit is in normal condition.)

Status of

Indication

Malfunction

Content of diagnosis

Inspection location/method

 

Remedy

indoor/

by LED1

No. dis-

 

 

 

 

 

outdoor

on out-

played on

 

 

 

 

 

units

door unit

main unit

 

 

 

 

 

 

*2

display sec-

 

 

 

 

 

 

 

tion *1

 

 

 

 

 

 

 

Main

Sub-

Main category

Sub-category

 

 

 

 

 

cate-

cate-

 

 

 

 

 

 

 

gory

gory

 

 

 

 

 

Indoor/

Nor-

0

0

 

Normal

 

outdoor

mal

 

 

 

 

 

 

 

units in

flash-

 

 

 

 

 

 

 

operation

ing

 

 

 

 

 

 

 

Indoor/

1 time

1

-0

Outdoor unit

Heat exchanger

(1) Measure resistance of the

(1)

Replace the outdoor

outdoor

 

 

 

thermistor

thermistor short-cir-

outdoor unit thermistors.

 

unit thermistor assem-

units in

 

 

 

short-circuit

cuit error

(TH2 to TH5: Approx. 4.4

 

bly.

complete

 

 

 

 

 

kΩ at 25°C)

 

 

shutdown

 

 

-1

 

Outside tempera-

(2) Check the lead wire of the

(2)

Replace the outdoor

 

 

 

 

 

ture thermistor

outdoor unit thermistor for

 

unit thermistor assem-

 

 

 

 

 

short-circuit error

torn sheath and short-cir-

 

bly.

 

 

 

 

 

 

cuit.

 

 

 

 

 

-2

 

Suction thermistor

(3) No abnormality found in

(3)

Replace the outdoor

 

 

 

 

 

short-circuit error

above inspections (1) and

 

unit control PWB

 

 

 

-3

 

2-way valve ther-

(2).

 

assembly.

 

 

 

 

 

mistor short-circuit

 

 

 

 

 

 

 

 

error

 

 

 

3 – 13

Image 7
Contents Models AY-XP7FR AE-X7FR AY-XP9FR AE-X9FR AY-XP12FR AY-XP7FR AE-X7FR SpecificationModel Indoor Unit Outdoor Unit Items AY-XP9FR AE-X9FR AY-XP9FR AE-X9FRAY-XP12FR AE-X12FR Indoor unit External DimensionOutdoor unit Indooa unit Outdooa unit Wiring DiagrmSelf-Diagnosis Function and Display Mode Troubleshooting GuideStatus AYXP7FR Main AYXP7FR Inter-unit wiring error mode Symptom AY-XP7FR Performance CurvesAY-XP9FR AY-XP12FR