Sharp AY-XP9FR, AY-XP12FR, AY-XP7FR, AE-X7FR, AE-X9FR, AE-X12FR service manual Status

Page 8

 

 

 

 

 

 

 

 

AYXP7FR

 

 

 

 

 

 

 

 

 

Status of

Indication

Malfunction

Content of diagnosis

Inspection location/method

 

Remedy

indoor/

by LED1

No. dis-

 

 

 

 

 

outdoor

on out-

played on

 

 

 

 

 

units

door unit

main unit

 

 

 

 

 

 

*2

display sec-

 

 

 

 

 

 

 

tion *1

 

 

 

 

 

 

 

Main

Sub-

Main category

Sub-category

 

 

 

 

 

cate-

cate-

 

 

 

 

 

 

 

gory

gory

 

 

 

 

 

Indoor/

2 times

2

-0

Cycle tempera-

Compressor high-

(1) Check the outdoor unit air

(1)

Ensure unobstructed

outdoor

 

 

 

ture

temperature error

outlet for blockage.

 

air flow from the out-

units in

 

 

 

 

 

 

 

door unit air outlet.

complete

 

 

 

 

 

(2) Check if the power supply

(2)

Connect power sup-

shutdown

 

 

 

 

 

voltage is 90 V or higher at

 

ply of proper voltage.

 

 

 

 

 

 

full power.

 

 

 

 

 

 

 

 

(3) Check the pipe connec-

(3)

Charge the specified

 

 

 

 

 

 

tions for refrigerant leaks.

 

amount of refrigerant.

 

 

 

 

 

 

(4) Measure resistance of the

(4)

Replace the outdoor

 

 

 

 

 

 

outdoor unit compressor

 

unit compressor ther-

 

 

 

 

 

 

thermistor.

 

mistor assembly.

 

 

 

 

 

 

(TH1: Approx. 53 kΩ at

 

 

 

 

 

 

 

 

25°C)

 

 

 

 

 

 

 

 

(5) Check the expansion

(5)

Replace the expan-

 

 

 

 

 

 

valve for proper operation.

 

sion valve coil, expan-

 

 

 

 

 

 

 

 

sion valve or outdoor

 

 

 

 

 

 

 

 

unit control PWB

 

 

 

 

 

 

 

 

assembly.

Indoor

 

 

-1

 

Temporary stop due

(Temporary stop for cycle pro-

 

unit in

 

 

 

 

to compressor dis-

tection)

 

 

operation

 

 

 

 

charge overheat *3

 

 

 

Outdoor

 

 

-2

 

Temporary stop due

(Temporary stop for cycle pro-

 

unit in

 

 

 

 

to outdoor unit heat

tection)

 

 

tempo-

 

 

 

 

exchanger overheat

 

 

 

rary stop

 

 

 

 

*3

 

 

 

 

 

 

-3

 

Temporary stop due

(Temporary stop for cycle pro-

 

 

 

 

 

 

to outdoor unit heat

tection)

 

 

 

 

 

 

 

exchanger overheat

 

 

 

 

 

 

 

 

*3

 

 

 

 

 

 

-4

 

Temporary stop due

(Temporary stop for cycle pro-

 

 

 

 

 

 

to 2-way valve

tection)

 

 

 

 

 

 

 

freeze *3

 

 

 

Indoor

3 times

3

-0

Dry operation

Temporary stop due

(Temporary stop for cycle pro-

 

unit in

 

 

 

 

to dehumidifying

tection)

 

 

operation

 

 

 

 

operation *3

 

 

 

Outdoor

 

 

 

 

 

 

 

 

unit in

 

 

 

 

 

 

 

 

tempo-

 

 

 

 

 

 

 

 

rary stop

 

 

 

 

 

 

 

 

Indoor/

5 times

5

-0

Outdoor unit

Heat exchanger

(1) Check connector CN8 of

(1)

Correct the installa-

outdoor

 

 

 

thermistor

thermistor open-cir-

the outdoor unit ther-

 

tion.

units in

 

 

 

open-circuit

cuit error

mistor for secure installa-

 

 

complete

 

 

 

 

 

tion.

 

 

shutdown

 

 

-1

 

Outside tempera-

(2) Measure resistance of out-

(2)

Replace the outdoor

 

 

 

 

 

ture thermistor

door thermistors TH1 to

 

unit thermistor assem-

 

 

 

 

 

open-circuit error

TH5.

 

bly.

 

 

 

-2

 

Suction thermistor

(3) Check the lead wires of

(3)

Replace the outdoor

 

 

 

 

 

open-circuit error

thermistors TH1 through

 

unit thermistor assem-

 

 

 

 

 

 

TH5 on the outdoor unit

 

bly.

 

 

 

 

 

 

control PWB for open-cir-

 

 

 

 

 

 

 

 

cuit.

 

 

 

 

 

-3

 

2-way valve ther-

(4) No abnormality found in

(5)

Replace the outdoor

 

 

 

 

 

mistor open-circuit

above inspections (1)

 

unit control PWB

 

 

 

 

 

error

through (3).

 

assembly.

 

 

 

-4

 

Discharge ther-

 

 

 

 

 

 

 

 

mistor open-circuit

 

 

 

 

 

 

 

 

error

 

 

 

3 – 14

Image 8
Contents Models AY-XP7FR AE-X7FR AY-XP9FR AE-X9FR AY-XP12FR Specification AY-XP7FR AE-X7FRAY-XP9FR AE-X9FR Model Indoor Unit Outdoor Unit Items AY-XP9FR AE-X9FRAY-XP12FR AE-X12FR Outdoor unit External DimensionIndoor unit Wiring Diagrm Indooa unit Outdooa unitTroubleshooting Guide Self-Diagnosis Function and Display ModeStatus AYXP7FR Main AYXP7FR Inter-unit wiring error mode Symptom AY-XP9FR Performance CurvesAY-XP7FR AY-XP12FR