HP T750J, T1000 G3, T1000J, T1500 G3, T750 G2, T1500J manual Options, DIP Switch Settings

Page 21

ADDITIONAL UPS FEATURES

Table 1 DIP Switch Settings

100V Models

Output Voltage

Input Voltage Range

DIP Switch 1

DIP Switch 2

 

 

 

 

100V

90–106V

ON

ON

 

 

 

 

 

120V Models

 

 

 

 

 

 

Output Voltage

Input Voltage Range

DIP Switch 1

DIP Switch 2

 

 

 

 

110V

99–116V

ON

OFF

 

 

 

 

120V*

108–127V*

OFF

OFF or ON

 

 

 

 

 

230V Models

 

 

 

 

 

 

Output Voltage

Input Voltage Range

DIP Switch 1

DIP Switch 2

 

 

 

 

220V

198–233V

ON

OFF

 

 

 

 

230V*

207–243V*

OFF

OFF or ON

 

 

 

 

240V

216–254V

ON

ON

* Default position

Options

The UPS is equipped with a USB port and a serial port. Either the USB port or the serial port may be used to monitor the UPS; however, they cannot operate simultaneously.

Port

The UPS can communicate with a USB-compliant computer using HP Power Manager software.

To establish communication between the UPS and a computer:

1Connect the USB cable to the USB port on the UPS rear panel.

Connect the other end of the USB cable to the USB port on your computer.

USB Port

Figure 15 The USB Port

2Install the HP Power Manager software according to the instructions provided with the software.

14

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002

Image 21
Contents Part Number 505922-002 July 2009 Second Edition Audience assumptions Page Regulatory compliance identification numbers Compliance noticesDischarge Japanese notice Battery replacement noticeGrounding methods to prevent electrostatic discharge Contents Shows the HP T750 G2 UPS 1IntroductionIntroduction Important Safety Instructions Safety Warnings3Installation UPS Internal BatteryEquipment Removing the Battery Cover Replace the metal battery cover Replace the UPS front bezelUPS If the UPS beeps or a UPS alarm indicator stays on, see onThis section shows the UPS rear panels Rear PanelsHP T750 G2, 230V Rear Panel HP T1500 G3, 230V Rear Panel UPS on Battery 4OperationUPS On UPS Off ModeFront Panel Self‐Test Configuration Additional UPS FeaturesOptions DIP Switch SettingsSerial Port Serial Port Pin Assignment Power Manager Software HP Power ManagerTransient Protector Battery Care UPS MaintenanceUPS and Batteries Disconnecting the Internal Battery ConnectorSpares Battery SparesBatteries Removing the Battery Cover New Batteries Used Battery or UPS Model List 7SpecificationsElectrical Output Battery Alarms and UPS Conditions 8TroubleshootingTroubleshooting Guide You Contact HP SupportContact Information Warranty Warranty InfromationComputer Load Protection Guarantee Battery Warranty