HP T1500J, T1000 G3, T1000J, T1500 G3, T750J, T750 G2 manual New Batteries

Page 29

UPS MAINTENANCE

New Batteries

5

3

Cable Retainer

4

Figure 24 Removing the Battery (HP T1000J, HP T1500J, HP T1500 G3 Models)

6Replace the battery. See “Recycling the Used Battery or UPS” on page 23 for proper disposal.

7Place the new battery pack in the same position with the battery terminals at the top.

8Connect the black battery cable to the new battery.

9Slide the batteries into the UPS. For HP T1000J, HP T1500 G3, and HP T1500J, carefully replace the black battery cable into the cable retainer.

C A U T I O N

To avoid damage to the battery leads, be sure that the cables do not bind against the guide rail while reinstalling the battery.

10Connect the red battery cable.

NOTE: A small amount of arcing may occur when connecting the batteries. This is normal and does not damage the unit or present any safety concern.

11Replace the metal battery cover and UPS front bezel.

NOTE: Allow batteries to charge for 6 to 24 hours before testing.

NOTE: The batteries must be fully charged and the UPS must not be in Battery mode to perform the self‐test.

Press and hold the (Test/Alarm Reset) button for three seconds to initiate a self-test. The 15-second test automatically distributes the load to the battery and tests the battery's performance. While the test is in progress, the indicators cycle through and the UPS beeps. When complete, the UPS returns to Normal mode as indicated by the ￿ (Power On) indicator.

If there is a problem with the battery, the UPS beeps, the + - (On Battery) indicator illuminates and the (Service) indicator flashes. Check the battery connections and be sure the battery is fully charged. Call your service representative if the problem persists.

22

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002

Image 29
Contents Part Number 505922-002 July 2009 Second Edition Audience assumptions Page Regulatory compliance identification numbers Compliance noticesDischarge Japanese notice Battery replacement noticeGrounding methods to prevent electrostatic discharge Contents Shows the HP T750 G2 UPS 1IntroductionIntroduction Important Safety Instructions Safety WarningsEquipment 3InstallationUPS Internal Battery Removing the Battery Cover Replace the metal battery cover Replace the UPS front bezelUPS If the UPS beeps or a UPS alarm indicator stays on, see onThis section shows the UPS rear panels Rear PanelsHP T750 G2, 230V Rear Panel HP T1500 G3, 230V Rear Panel UPS On UPS on Battery4Operation Front Panel UPS OffMode Self‐Test Configuration Additional UPS FeaturesOptions DIP Switch SettingsSerial Port Serial Port Pin Assignment Transient Protector Power Manager SoftwareHP Power Manager Battery Care UPS MaintenanceUPS and Batteries Disconnecting the Internal Battery ConnectorSpares Battery SparesBatteries Removing the Battery Cover New Batteries Used Battery or UPS Model List 7SpecificationsElectrical Output Battery Alarms and UPS Conditions 8TroubleshootingTroubleshooting Guide You Contact HP SupportContact Information Warranty Warranty InfromationComputer Load Protection Guarantee Battery Warranty