SPECIFICATIONS

Table 8 Battery

UPS Configuration

HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries

 

HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries

 

HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries

 

 

Voltage

HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc

 

HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc

 

 

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

 

 

Charging

Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line

 

and no supplementary power supply load

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning

 

 

Table 9 Battery Runtimes (in Minutes)

 

 

 

UPS Models by VA Ratings

 

 

 

 

 

 

Load (VA)

Watts

750

1000

1400

 

 

 

 

 

200

128

38

41

58

 

 

 

 

 

300

192

27

28

41

 

 

 

 

 

500

320

14

15

28

 

 

 

 

 

600

402

9

10

19

 

 

 

 

 

750

503

6

8

14

 

 

 

 

 

900

603

 

6

10

 

 

 

 

 

1000

670

 

5

8

 

 

 

 

 

1200

804

 

 

6

 

 

 

 

 

1400

938

 

 

5

 

 

 

 

 

NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.

26

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002

Image 33
Contents Part Number 505922-002 July 2009 Second Edition Audience assumptions Page Regulatory compliance identification numbers Compliance noticesDischarge Japanese notice Battery replacement noticeGrounding methods to prevent electrostatic discharge Contents Shows the HP T750 G2 UPS 1IntroductionIntroduction Important Safety Instructions Safety Warnings3Installation UPS Internal BatteryEquipment Removing the Battery Cover Replace the metal battery cover Replace the UPS front bezelUPS If the UPS beeps or a UPS alarm indicator stays on, see onThis section shows the UPS rear panels Rear PanelsHP T750 G2, 230V Rear Panel HP T1500 G3, 230V Rear Panel UPS on Battery 4OperationUPS On UPS Off ModeFront Panel Self‐Test Configuration Additional UPS FeaturesOptions DIP Switch SettingsSerial Port Serial Port Pin Assignment Power Manager Software HP Power ManagerTransient Protector Battery Care UPS MaintenanceUPS and Batteries Disconnecting the Internal Battery ConnectorSpares Battery SparesBatteries Removing the Battery Cover New Batteries Used Battery or UPS Model List 7SpecificationsElectrical Output Battery Alarms and UPS Conditions 8TroubleshootingTroubleshooting Guide You Contact HP SupportContact Information Warranty Warranty InfromationComputer Load Protection Guarantee Battery Warranty