HP Performance Optimized Data Center (POD) 40cp manual HP POD control power

Page 17

Component

Quantity

Phases

Amps

Volts

Description

 

 

 

 

 

 

 

 

 

 

 

the HP POD.

 

 

 

 

 

 

Primary feeders

3

3

225

415/240

Supply power path to IT equipment.

 

 

 

 

 

 

Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3- phase, 415V wye power, and switchboards to distribute feeder inputs to the HP POD.

NOTE: For locations outside North America, consult with HP regarding the requirements and specifications of transformers.

The customer must supply one 1200A, 480V delta, 3-phase feeder to the transformer that will supply 415V 3 phase power to the HP POD.

Final connections to the HP POD can be supplied by the customer or by HP at additional costs.

HP POD control power

HP POD control power is supplied by two redundant power house panels that are supplied with:

3-phase

380 to 415V wye connected

50 to 60 Hertz

100A

NOTE: Only one control power panel is required in the non-redundant power path configuration.

All 3-phase HP POD feeders require that the neutrals and the equipment grounding conductors remain isolated. Bonding of the two conductors is allowed at the power source only.

Power management 17

Image 17
Contents Part Number March 2010 Second Edition Intended audience Contents Site requirements Safety informationAbout this document Site preparationDescription PowerSystem utilities Optional connections to central facility infrastructure Environmental specificationsDrainage Environmental considerationsLightning protection Dimensions HP POD specificationsWeight External cold aisle viewTop view Required clearancesDouble door end view Callout Feature Water input side view Callout FeatureExternal hot aisle view Water supply specificationsFeature Specification Water quality requirements Water quality requirements and specificationsAcceptable water quality specifications Piping materials Water precautionsCondensation management Power requirements Power managementConnection requirements Standard density HP PODComponent Quantity Phases Amps Volts Description Standard density HP POD with redundant powerHigh density HP POD High density HP POD with redundant powerHP POD control power Supported facility connections Humidifier specificationsConvenience outlets Grounding requirementsHP POD Environmental Control System IT cable portalsHP POD security EPO Fire, safety, and security notificationsAcronyms and abbreviations