HP Performance Optimized Data Center (POD) 40cp Standard density HP POD with redundant power

Page 15

Standard density HP POD with redundant power

Component

Quantity

Phases

Amps

Volts

Description

 

 

 

 

 

 

Primary feeders

2

3

225

415/240

Supply primary power path to IT

 

 

 

 

 

equipment.

 

 

 

 

 

 

House power

2

3

100

415/240

One 100A feed to house panel A

feeders

 

 

 

 

to power HP POD ECS,

 

 

 

 

 

convenience outlet, lighting, and

 

 

 

 

 

auxiliary equipment provided with

 

 

 

 

 

the HP POD.

 

 

 

 

 

The second 100A feed supplies an

 

 

 

 

 

alternate source of power to house

 

 

 

 

 

panel B if power path A fails.

 

 

 

 

 

All house panel loads are supplied

 

 

 

 

 

from either house power panel A or B

 

 

 

 

 

through high speed contactors.

 

 

 

 

 

 

Redundant

2

3

225

415/240

Supply secondary power path to IT

feeders

 

 

 

 

equipment.

 

 

 

 

 

 

Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3- phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.

NOTE: For locations outside North America, consult with HP regarding the requirements and specifications of transformers.

The customer must supply two 480V, 450A feeders to the transformers that will supply 415V 3-phase power to the HP POD. Each power source is capable of supporting the HP POD in the event of a power failure or planned maintenance.

Final connections to the HP POD can be supplied by the customer or by HP at additional cost.

Standard density HP POD without redundancy

Component

Quantity

Phases

Amps

Volts

Description

 

 

 

 

 

 

Primary

2

3

225

415/240

Supply primary power path to IT

feeders

 

 

 

 

equipment

 

 

 

 

 

 

House power

1

3

100

415/240

House panel A supplies power to HP POD

feeders

 

 

 

 

ECS, convenience outlet, lighting, and

 

 

 

 

 

auxiliary equipment provided with the HP

 

 

 

 

 

POD.

 

 

 

 

 

 

Primary

2

3

225

415/240

Supply power path to IT equipment

feeders

 

 

 

 

 

 

 

 

 

 

 

Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3- phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.

NOTE: For locations outside North America, consult with HP regarding the requirements and specifications of transformers.

The customer must supply one 480V, 3-phase, 800A feeder to the transformer that will supply 415V 3 phase power to the HP POD.

Final connections to the HP POD can be supplied by the customer or by HP at additional costs.

Power management 15

Image 15
Contents Part Number March 2010 Second Edition Intended audience Contents Site preparation Safety informationSite requirements About this documentPower System utilitiesDescription Environmental considerations Environmental specificationsOptional connections to central facility infrastructure DrainageLightning protection External cold aisle view HP POD specificationsDimensions WeightTop view Required clearancesDouble door end view Callout Feature Water input side view Callout FeatureWater supply specifications Feature SpecificationExternal hot aisle view Water quality requirements and specifications Acceptable water quality specificationsWater quality requirements Water precautions Condensation managementPiping materials Standard density HP POD Power managementPower requirements Connection requirementsComponent Quantity Phases Amps Volts Description Standard density HP POD with redundant powerHigh density HP POD High density HP POD with redundant powerHP POD control power Grounding requirements Humidifier specificationsSupported facility connections Convenience outletsIT cable portals HP POD securityHP POD Environmental Control System EPO Fire, safety, and security notificationsAcronyms and abbreviations
Related manuals
Manual 63 pages 13.75 Kb Manual 79 pages 43.3 Kb