HP Performance Optimized Data Center (POD) 40cp manual Power management, Connection requirements

Page 14

Power management

Connection requirements

When determining the final location of your power and water connections, consider the distance between the facility utilities and the HP POD.

The facility power connection must be installed in compliance with local electrical codes and regulations. HP reference electrical installation design is based on a maximum distance of 15.2 m (50 ft) or line of sight between the switchboard and the HP POD.

HP can provide engineering services to develop the site installation plan and drawings as a supplemental service.

All 3-phase HP POD feeders require that the neutrals and the equipment grounding conductors remain isolated. Bonding of the two conductors is allowed at the power source only.

Power requirements

The HP POD is available in both standard and high density models.

North America

The standard density HP POD can be configured for 291 kW redundant power paths for maximum reliability or 380 kW power paths for maximum capacity.

The high density HP POD can be configured for 380 kW redundant power paths for maximum reliability or 600 kW power paths for maximum capacity.

International

The standard density HP POD can be configured for 291 kW redundant power paths for maximum reliability or 450 kW power paths for maximum capacity.

The high density HP POD can be configured for 436 kW redundant power paths for maximum reliability or 600 kW power paths for maximum capacity.

Standard density HP POD

The standard density HP POD must be supplied with four feeders.

3-phase

380 to 415V wye connected

225A

50 to 60 Hz

Each feeder must contain three phase conductors, one neutral conductor, and one equipment ground conductor.

Power management 14

Image 14
Contents Part Number March 2010 Second Edition Intended audience Contents About this document Safety informationSite requirements Site preparationDescription PowerSystem utilities Drainage Environmental specificationsOptional connections to central facility infrastructure Environmental considerationsLightning protection Weight HP POD specificationsDimensions External cold aisle viewRequired clearances Top viewWater input side view Callout Feature Double door end view Callout FeatureExternal hot aisle view Water supply specificationsFeature Specification Water quality requirements Water quality requirements and specificationsAcceptable water quality specifications Piping materials Water precautionsCondensation management Connection requirements Power managementPower requirements Standard density HP PODStandard density HP POD with redundant power Component Quantity Phases Amps Volts DescriptionHigh density HP POD with redundant power High density HP PODHP POD control power Convenience outlets Humidifier specificationsSupported facility connections Grounding requirementsHP POD Environmental Control System IT cable portalsHP POD security Fire, safety, and security notifications EPOAcronyms and abbreviations