Power Requirements

PANDUIT® DPoE™ Power Patch Panel User’s Guide

Issue 2.2

 

Part Number: PN378A

 

 

9.Lay conductors into the punchdown slots for the specified port using the correct wiring sequence. Cable jacket removal should be minimized to the extent possible. Conductor untwist should be within ½” (12.7 mm) of termination.

WARNING:

NEVER TOUCH UNINSULATED COMMUNICATIONS WIRING OR TERMINALS UNLESS THE COMMUNICATION LINE HAS BEEN DISCONNECTED AT THE NETWORK INTERFACE.

NOTE:

Never install wiring in a slot previously used for a larger gauge wire.

10.Using the punchdown tool (PANDUIT part number PDT110), punch down the connector into the punchdown slots on the back of the DPoE™ Power

Patch Panel.

Power Requirements

11.If the panel is being powered by a PANDUIT® DPoE™ Power Brick (See page 8, Table 1: Power Supplies Available from PANDUIT Corp for a list of available powering options), skip to Powering Up the DPoEPower Patch Panel Section below, since the brick is equipped with a matched keyed power connector that will fit the power connector on the back of the panel.

12.If the PANDUIT® DPoE™ Power Chassis or a direct 48VDC source is powering the panel, cut the 10-foot power harness to length then strip the ends of the leads to 5/16” (7.9 mm). Connect the stripped ends of the power harness into the PANDUIT® DPoE™ Power Chassis. If the power harness is not long enough or the 48VDC source requires a specific connector, strip the ends of the wire to the same strip length, being careful not to damage the conductors.

13.Using the two butt splices provided with the panel, and paying attention to the polarity of the supply voltage, crimp the power harness wires to the supply wires. A crimping tool, such as the PANDUIT part number CT-100, may be used. The provided butt splices (PANDUIT part number BSV14X) support 14-16 AWG solid or stranded wire.

13