Panduit DPOE12U1XY, DPOE24S1XY, DPOE24U1XY manual DPoE Power Patch Panel Firmware Update

Models: DPOE12U1X DPOE24S1X DPOE24U1XY DPOE12U1XY DPOE24S1XY DPOE24U1X

1 64
Download 64 pages 2.84 Kb
Page 50
Image 50
DPoE™ Power Patch Panel Firmware Update

PANDUIT® DPoE™ Power Patch Panel User’s Guide

Issue 2.2

 

Part Number: PN378A

 

 

If the Online indicator is not checked (Manual background ), the EM assumes it is in the offline mode and will not attempt to connect to the deployed Patch Panel Network. Changes made within the EM will not be updated in the panels.

When the power consumed on any given panel reaches the Power Warning Threshold below the maximum power level for that particular panel, the panel will issue a warning alarm and display that the panel is in the warning range.

NOTE:

This above setting is a system-wide power warning threshold, but it used as a percentage below maximum for each individual panel. Some panels in the network might have their maximum panel power set at different levels and therefore would alarm at different points. (See page 33, Edit Panel Information, for more information on the Power Threshold field.)

Rack Space Numbering is a system-wide field {ascending, descending} that enables the EM to display the panels in the racks in the same fashion as they are wired in the network racks. Either the rack slots are numbered from with the highest rack positions at the top (descending) or the highest rack positions at the bottom (ascending). By setting this parameter appropriately, the rack-level displays presented by the EM will show the DPoE™ Power Patch Panels in their installed top-to-bottom order.

The SNMP Timeout Value is a configurable threshold. If more than this number of seconds has expired and the system hasn’t yet received an answer to a previously transmitted SNMP message, the system will assume there is a communications problem.

DPoE™ Power Patch Panel Firmware Update

The DPoE™ Power Patch Panel has the ability to have its firmware programmed remotely. A Trivial File Transfer Protocol (TFTP) operation can be initiated using the Element Manager (EM). The Firmware Update option under the Tools pull-down menu provides a method to perform the update.

NOTE:

The latest version of firmware may be downloaded after product registration at www.panduit.com/ManagedNetworkSolutions

The panduit.com website will allow users to download firmware updates to their own TFTP server.

49

Page 50
Image 50
Panduit DPOE12U1XY, DPOE24S1XY, DPOE24U1XY manual DPoE Power Patch Panel Firmware Update