HP Performance Optimized Data Center (POD) 40cp manual IT cable portals, HP POD security

Page 19

IMPORTANT: For full protection, you must ground the HP POD, power distribution components and the water distribution kit to your ground grid system.

IT cable portals

Six 6.35 cm (2 ½-inch) IT cable portals on each side of the HP POD are available for optional Ethernet, fiber optic, and IT cable configuration. These components are also used for ECS connections and can support dedicated lines, a customer network, and various other communications service options. You can install a weatherproof box for termination points over the cable portals on the outside of the HP POD.

Examples of cables that can run into the 6.35 cm (2 ½ inch) portals are as follows:

48 Cat-6 cables

39 12 strand multi-mode or single-mode fiber optic cables

HP POD security

The HP POD is equipped with standard key lock hardware at each entry door and external panel. Conduit and junction boxes are provided for customer installed controlled access systems.

Optional controlled access security includes a 12-digit security code keypad and magnetic locks on each entry door.

HP POD Environmental Control System

The HP POD ECS is a stand-alone system that does not require any connections to existing facility management infrastructure. You can choose to connect to the facility BMS at an additional cost. BMS configuration communicates through an Ethernet cable connected to the internal HP POD ECS panel jack located underneath the IT cable portals. HP POD ECS data can be sent and viewed using a set IP address.

The HP POD ECS communicates through the standard BMS protocol, which is a data communication protocol for building automation and control networks.

Supported facility connections 19

Image 19
Contents Part Number March 2010 Second Edition Intended audience Contents Site preparation Safety informationSite requirements About this documentSystem utilities PowerDescription Environmental considerations Environmental specificationsOptional connections to central facility infrastructure DrainageLightning protection External cold aisle view HP POD specificationsDimensions WeightTop view Required clearancesDouble door end view Callout Feature Water input side view Callout FeatureFeature Specification Water supply specificationsExternal hot aisle view Acceptable water quality specifications Water quality requirements and specificationsWater quality requirements Condensation management Water precautionsPiping materials Standard density HP POD Power managementPower requirements Connection requirementsComponent Quantity Phases Amps Volts Description Standard density HP POD with redundant powerHigh density HP POD High density HP POD with redundant powerHP POD control power Grounding requirements Humidifier specificationsSupported facility connections Convenience outletsHP POD security IT cable portalsHP POD Environmental Control System EPO Fire, safety, and security notificationsAcronyms and abbreviations