HP Performance Optimized Data Center (POD) 20cp manual Removal and replacement procedures

Page 20

2.Disconnect the PDUs that are connected to the busway drop box (2).

3.Use a socket wrench to loosen and remove the bolt securing the busway drop box to the retaining hardware bracket (1).

4.Slide the hardware bracket to the right along the busway, completely disconnecting it from the busway drop box (2).

WARNING: Use caution when removing and replacing the busway drop box. The drop box weighs approximately 9 kg (20 lb).

5.Rotate the busway drop box 90° so that it is perpendicular to the electrical busway, and then remove the drop box from the electrical busway (3).

Removal and replacement procedures 20

Image 20
Contents Abstract Page Contents Contacting HP Illustrated parts catalog Structural component identificationLife safety component identification Component DescriptionElectrical power component identification Front view shown Component DescriptionAccessed only by authorized personnel Electrical safety label Description Control cabinet component identificationCold aisle clearance HP POD 20c racksAisle clearances Replaceable components for China models Hot aisle clearanceSpare part number Description Installation considerations Optional Fire suppression system OverviewRemoval and replacement procedures ButtonsEPO button Removing the EPO buttonRemoving the control relay module DIN rail componentsControl relay module Differential pressure sensor Replacing the control relay moduleRemoving the differential pressure sensor Replacing the differential pressure sensorDoor position devices Magnetic contactsRemoving the magnetic contacts Replacing the magnetic contactsRemoving the busway drop box ElectricalBusway drop box Removal and replacement procedures Replacing the busway drop box Fans IT cooling fanRemoving the IT cooling fan Ventilation fan Replacing the IT cooling fanRemoving the Rittal SK 3326 ventilation fan Replacing the Rittal SK 3326 ventilation fanFilters Heat exchanger air filtersRemoving the heat exchanger air filter Replacing the heat exchanger air filterVesda filter Removing the Vesda filterRittal SK 3326 ventilation fan filter Replacing the Vesda filterRemoving the Rittal SK 3326 ventilation fan filter Replacing the Rittal SK 3326 ventilation fan filterIndicators ECS touchscreen and EPO indicatorsRemoving the ECS EPO LED indicators Replacing the ECS EPO LED indicatorsLights LED lightRemoving the LED light Replacing the LED lightRemoving the drain pan sensor SensorsHeat exchanger condensate drain pan sensors Chilled water supply and return header drain pan sensors Replacing the drain pan sensorHumidistat Removing the humidistatReplacing the humidistat Humidity sensor Removing the humidity sensor Replacing the humidity sensorChilled water system temperature sensor Removing temperature sensor from the chilled water systemChilled water temperature sensor internal components Replacing the temperature sensor in the chilled water systemReplace the chilled water temperature sensor circuit board Removal and replacement procedures Replacing the cold aisle temperature sensor Temperature sensor cold aisleRemoving the cold aisle temperature sensor Temperature sensors hot aisle Removing the hot aisle temperature sensorChilled water supply and return header pressure sensors Replacing the hot aisle temperature sensorFluid system components You need a wrench to remove and replace the pressure sensors Replacing the chilled water flow sensor Chilled water flow sensorRemoving the chilled water flow sensor Chilled water system temperature sensor Chilled water temperature sensor internal components Replace the chilled water temperature sensor circuit board Heat exchanger Humidifier Removing the humidifierRemoval and replacement procedures Replacing the humidifier Removal and replacement procedures Humidistat if installed Replacing the humidistat Removing the external chilled water isolation valve ValvesExternal chilled water isolation valve Removing the external pressure gauge isolation valve External pressure gauge isolation valveReplacing the external chilled water isolation valve Replacing the external pressure gauge isolation valve Periodic maintenance Periodic maintenance overviewQualified personnel Cooling systemLeak detection Leak isolationHumidifier if installed ECS POD Shut Down Required Fire alarm and suppression system HP POD 20c structureLife safety EPO Functional TestAccess control Third-party componentsElectrical specifications SpecificationsGeneral HP POD 20c specifications Rack specifications Environmental specificationsWater specifications Thermal and air flow performanceOptional features specifications HP contact information Contacting HPBefore you contact HP HP POD 20c regulatory compliance Safety and NEC complianceRegulatory information Regulatory requirements for Exit signs With Council, Inc Regulatory information Glossary Branch circuitSOW Documentation feedback Index HP POD 20c structure Temperature sensors, cold aisle
Related manuals
Manual 86 pages 43.14 Kb Manual 22 pages 15.98 Kb Manual 37 pages 24.34 Kb Manual 38 pages 28.4 Kb